Modular distribution terminals, PUSH IN, 6 mm², 500 V, 41 A, dark beige
Technical Specifications:
| Depth | 47 mm |
| Depth (inches) | 1.85 inch |
| Depth including DIN rail | 48 mm |
| Height | 85.5 mm |
| Height (inches) | 3.366 inch |
| Width | 8.1 mm |
| Width (inches) | 0.319 inch |
| Net weight | 21.05 g |
| Storage temperature | -25 °C…55 °C |
| Ambient temperature | -5 °C…40 °C |
| Continuous operating temp., min. | -60 °C |
| Continuous operating temp., max. | 130 °C |
| RoHS Compliance Status | Compliant without exemption |
| REACH SVHC | No SVHC above 0.1 wt% |
| Material | Wemid |
| Colour | dark beige |
| Colour of operational elements | orange |
| UL 94 flammability rating | V-0 |
| Marking EN 60079-7 | Ex ec II C Gc |
| Ex 2014/34/EU label | II 2 G D |
| End cover plate required | Yes |
| Number of potentials | 1 |
| Number of levels | 1 |
| Number of clamping points per level | 7 |
| Number of potentials per tier | 1 |
| Levels cross-connected internally | No |
| PE connection | No |
| Rail | TS 35 |
| N-function | No |
| PE function | No |
| PEN function | No |
| Explosion-tested version | Yes |
| Installation advice | Rail |
| Open sides | right |
| Snap-on | Yes |
| Type of fixing | Snap-on |
| Type of mounting | TS 35 |
| Blade size, additional connection | 0.4 x 2.0 mm |
| Clamping range, further connection, max. | 1.5 mm² |
| Clamping range, further connection, min. | 0.14 mm² |
| Conductor cross-section, flexible plus plastic collar DIN 46228/1, further connection, max. | 1.5 mm² |
| Conductor cross-section, flexible plus plastic collar DIN 46228/1, further connection, min. | 0.5 mm² |
| Conductor cross-section, flexible, further connection, min. | 0.5 mm² |
| Connection direction | top |
| Connection type, additional connection | PUSH IN |
| Cross-section for connected wire, flexible, further connection, max. | 1.5 mm² |
| Cross-section for connected wire, multi-core, further connection, max. | 1.5 mm² |
| Cross-section for connected wire, multi-core, further connection, min. | 0.5 mm² |
| Cross-section for connected wire, solid-core, further connection, max. | 1.5 mm² |
| Cross-section for connected wire, solid-core, further connection, min. | 0.5 mm² |
| Number of connections, additional connection | 6 |
| Rated cross-section, further connection | 1.5 mm² |
| Rated current, additional connection | 17.5 A |
| Stripping length , additional connection | 8 mm |
| Blade size | 1.0 x 5.5 mm |
| Clamping range, max. | 6 mm² |
| Clamping range, min. | 0.34 mm² |
| Connection cross-section, stranded, max. | 6 mm² |
| Connection cross-section, stranded, min. | 0.5 mm² |
| Connection direction | top |
| Gauge to IEC 60947-1 | A5 |
| Number of connections | 1 |
| Stripping length | 12 mm |
| Tube length for twin wire-end ferrule | Tube length: min.: 10 mm max.: 12 mm Cross-section for conductor connection: nominal: 0.5 mm² Tube length: min.: 10 mm max.: 18 mm Cross-section for conductor connection: nominal: 0.75 mm² Tube length: min.: 12 mm max.: 18 mm Cross-section for conductor connection: min.: 1 mm² max.: 1.5 mm² |
| Tube length for wire-end ferrule with plastic collar DIN 46228/4 | Tube length: min.: 10 mm max.: 12 mm Cross-section for conductor connection: min.: 0.5 mm² max.: 1 mm² Tube length: min.: 10 mm max.: 18 mm Cross-section for conductor connection: nominal: 1.5 mm² Tube length: min.: 12 mm max.: 18 mm Cross-section for conductor connection: nominal: 2.5 mm² Tube length: min.: 10 mm max.: 18 mm Cross-section for conductor connection: min.: 4 mm² max.: 6 mm² |
| Tube length for wire-end ferrule without plastic collar DIN 46228/1 | Tube length: nominal: 10 mm Cross-section for conductor connection: min.: 0.5 mm² max.: 1 mm² Tube length: min.: 10 mm Cross-section for conductor connection: min.: 1.5 mm² max.: 2.5 mm² Tube length: min.: 12 mm max.: 18 mm Cross-section for conductor connection: nominal: 4 mm² Tube length: min.: 10 mm max.: 18 mm Cross-section for conductor connection: min.: 6 mm² max.: 10 mm² |
| Twin wire-end ferrules, max. | 1.5 mm² |
| Twin wire-end ferrules, min. | 0.5 mm² |
| Type of connection | PUSH IN |
| Type of connection 2 | PUSH IN |
| Wire connection cross section AWG, max. | AWG 8 |
| Wire connection cross section AWG, min. | AWG 22 |
| Wire connection cross section, finely stranded, max. | 6 mm² |
| Wire connection cross section, finely stranded, min. | 0.5 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max. | 6 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min. | 0.5 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. | 6 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. | 0.5 mm² |
| Wire connection cross-section, solid core, max. | 6 mm² |
| Wire connection cross-section, solid core, min. | 0.5 mm² |
| Installation advice | Rail |
| Number of poles | 1 |
| Rail | TS 35 |
| Standards | IEC 60947-7-1 |
| Wire connection cross section AWG, max. | AWG 8 |
| Wire connection cross section AWG, min. | AWG 22 |
| Rated cross-section | 6 mm² |
| Rated voltage | 500 V |
| Rated AC voltage | 500 V |
| Rated DC voltage | 500 V |
| Rated current | 41 A |
| Current at maximum wires | 41 A |
| Standards | IEC 60947-7-1 |
| Volume resistance according to IEC 60947-7-x | 0.78 mΩ |
| Rated impulse withstand voltage | 6 kV |
| Power loss in accordance with IEC 60947-7-x | 1.31 W |
| Pollution severity | 3 |
| Surge voltage category | III |
| Product information | The applicable safety regulations for the overload and short-circuit of the connected conductors must be followed. The total current of all connected conductors must not exceed the max. load current. |