Installation cable, Cat.5 (ISO/IEC 11801) / Cat.5e (TIA T568-B), PVC, 500 m
Technical Specifications:
| Length | 500 m |
| Length (inches) | 19,685.039 inch |
| Net weight | 11,250 g |
| Storage temperature | -40 °C…75 °C |
| Operating temperature | -40 °C…80 °C |
| Installation temperature | 0 °C…50 °C |
| RoHS Compliance Status | Compliant without exemption |
| REACH SVHC | No SVHC above 0.1 wt% |
| Insulation | PE |
| Number of poles | 8 |
| Number of wires | 8 |
| Resistance to oils | No |
| Resistance to spread of flame | in accordance with IEC 60332-1 EN 13501-6 class ECa |
| Sheathing colour | green (RAL 6018) |
| Shielded | Yes |
| Test voltage wire-wire-shield | 700 V AC |
| Impervious to smoke | No |
| Impervious to smoke | No |
| Arrangement of wire cores | Twisted pair |
| Colour sequence or wires – wire pairs | white/blue – blue, white/orange – orange, white/green – green, white/brown – brown |
| Complete shielding | Aluminium foil Shielding braid made from copper wiring |
| Cross-section | 4*2*AWG 24/1 – 4*2*0.205 mm² |
| Insulation | PE |
| Insulation cross-section | 1.04 mm |
| Material sheath | PVC |
| Number of wires | 8 |
| Overlap of shielding braid | 65 % |
| Sheath diameter, max. | 6.7 mm |
| Sheath diameter, min. | 6.3 mm |
| Sheathing colour | green (RAL 6018) |
| Sheathing material thickness | 0.5 mm |
| Shielding | SF/UTP |
| Shielding braid thickness | 0.1 mm |
| Standard designations | SF/UTP |
| Strands | 1 |
| Wire core insulation thickness | 0.25 mm |
| Wire material | Non-insulated copper wire |
| Capacity at 1 kHz | 50 nF/km |
| Category | Cat.5 (ISO/IEC 11801) / Cat.5e (TIA T568-B) |
| Characteristic impedance | 100 ± 5 Ω at 100MHz |
| Delay skew | 15 ns/100m |
| Loop resistance | 190 Ω/km |
| Resistance differential | 3 % |
| Shield attenuation | 65 dB at 100 Mhz |
| Signal propagation time | 4.5 ns/m |
| Test voltage wire-wire-shield | 700 V AC |
| Transfer impedance | 20 mΩ/m at 1MHz 10 mΩ/m at 10 MHz 10 mΩ/m at 30Mhz |
| Abrasion resistance | good |
| Colour | green |
| Fire propagation | No |
| Impervious to smoke | No |
| Min. bending radius, once only | 5 x cable diameter |
| Min. bending radius, repetitive | 10 x cable diameter |
| Resistance to oils | No |
| Resistance to spread of flame | in accordance with IEC 60332-1 EN 13501-6 class ECa |





Reviews