Weidmueller TFIS 12-240VUC 2NO SD

Request a price

TFIS 12-240VUC 2NO SD

SKU: 2697270000.0 Category: Brand:

TFI-SERIES, Star-Delta Timer, Number of contacts: 2, NO contact, AgNi, Rated control voltage: 12…240 V UC -10 % / +10 %, Continuous current: 3 A, Screw connection

Technical Specifications:

Depth 75 mm
Depth (inches) 2.953 inch
Height 67 mm
Height (inches) 2.638 inch
Width 225 mm
Width (inches) 8.858 inch
Net weight 81 g
Storage temperature -40 °C…70 °C
Operating temperature -25 °C…60 °C
Humidity 5…95 % rel. humidity, no condensation
RoHS Compliance Status Compliant without exemption
REACH SVHC No SVHC above 0.1 wt%
Rated control voltage 12…240 V UC -10 % / +10 %
Power rating 500 mVA 180 mW
Status indicator LED green (U/t) flashes: star-relay closed, time runs LED green (U/t) lights permanently: delta-relay closed, time runs LED yellow (R): star-relay closed
Time ranges 0.5 s – 10 s 1.5 s – 30 s 3 s – 60 s 9 s – 180 s
Setting tolerance 5 %
Max. reset time after voltage interruption 200 ms
Basic accuracy ± 1 % (of scale-end value)
Min. pulse duration 100 ms
Repeat accuracy <0.5 % or ±5 ms
Rated switching voltage 250 V AC
Continuous current 3 A
Max. switching voltage, AC 250 V
Max. switching voltage, DC 30 V
Min. switching power 10 mA @ 12 V 100 mA @ 5 V
AC switching capacity (resistive), max. 750 VA
DC switching capacity (resistive), max. 90 W
Contact type 2 NO contact (AgNi)
Electrical service life, DC coil 100×103 switching cycles (3 A at 250 VAC)
Mechanical service life 20 x 106 switching cycles
Suitable for front mounting No
Rail TS 35
Test button available No
Mechanical switch position indicator No
Colour black
UL 94 flammability rating V-0
UL94 flammability rating component Component: Housing UL94 flammability rating: V-0
Resistance to vibration EN 61812-1 10 Hz…60 Hz: 0.15 mm 60 Hz…150 Hz: 2 g
Rated voltage 300 V
Pollution severity 2
Surge voltage category III
Clearance and creepage distances for control side – load side ≥ 3 mm
Dielectric strength for control side – load side 1.6 kV
Impulse withstand voltage 4 kV
Protection degree IP20
Certificate no. (cULus) E360862
Wire connection method Screw connection
Stripping length, rated connection 8 mm
Tightening torque, max. 1 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 4 mm²
Wire connection cross section AWG, min. AWG 20
Wire connection cross section AWG, max. AWG 12
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, solid, max. 4 mm²
Wire connection cross section, finely stranded, min. 0.5 mm²
Wire connection cross section, finely stranded, max. 4 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min. 0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 2.5 mm²
Wire connection cross section, finely stranded, two clampable wires, min. 0.5 mm²
Wire cross-section, finely stranded, two clampable wires, max. 2.5 mm²