Safety relay, 24 V DC ± 20%, , Max. switching current, internal fuse : , Safety category: SIL 3 EN 61508:2010
Technical Specifications:
| Depth | 119.2 mm |
| Depth (inches) | 4.693 inch |
| Height | 113.6 mm |
| Height (inches) | 4.472 inch |
| Width | 17.5 mm |
| Width (inches) | 0.689 inch |
| Net weight | 218 g |
| Storage temperature | -40 °C…85 °C |
| Operating temperature | -40 °C…50 °C |
| Humidity | 95 %, no condensation |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 807f1906-ce90-4f93-8801-4b128b343e6b |
| Connection designation | 0V 24 V |
| Rated control voltage | 24 V DC ±20 % |
| Current consumption | < 40 mA + M14 |
| Protective circuit | Reverse polarity protection |
| Connection designation (safety circuit) | A1 A2 |
| Rated control voltage | 24 V DC ± 20% |
| Current consumption | 56 mA |
| Status indicator | LED yellow (RLY): lights up when input circuit (A1,A2) of the device is actuated |
| Protective circuit | Reverse polarity protection Free-wheeling diode |
| Connection designation (safety test) | T1 T2 T3 |
| Rated control voltage | 24 V DC ±20 % |
| Number of test inputs | 3 |
| Connection designation (safety output) | L N 13 14 |
| Contact design | 1 x energised to safe (NO contact) |
| Contact base material | AgNi gold flashed |
| Max. permitted switching voltage | 250 V AC |
| Max. switching current, external fuse | 2,5 A |
| Max. switching capacity | 625 VA |
| External back-up fuse | 2.5 A (slow blow) |
| Switch-on time | 50 ms |
| Min. switching capacity | 30 mA @ 15 V |
| Connection designation (Alarm output) | M13 M14 |
| Digital output (Alarm output) | 1 DO |
| Solid-state type (Alarm output) | MOS-FET high-active |
| output current, max. (Alarm output) | 100 mA |
| Short-circuit-proof (Alarm output) | Yes, without time limit |
| Voltage drop at max. load (Alarm output) | 1.5 V |
| Status indicator (Alarm output) | LED red (ERR): flashes when device detects a fault, supply voltage applied and input circuit (A1, A2) not actuated |
| Connection designation (Diagnostic output) | D21 D22 |
| Switching voltage, max.(Diagnostic output) | 30 V |
| Switching, current, max. (Diagnostic output) | 100 mA |
| switching capacity, min. (Diagnostic output) | 1 mW |
| Contact design (Diagnostic output) | 1 NC contact |
| Contact material (Diagnostic output) | AgNi gold-plated |
| Status indicator (Diagnostic output) | LED green (DIAG): lights up when supply voltage applied and input circuit (A1, A2) not actuated |
| Device type | A |
| Safety category | SIL 3 |
| Safety standard | EN 61508:2010 |
| Operating altitude | ≤ 2000 m above sea level |
| Rail | TS 35 |
| Colour | black yellow |
| Insulation coordination according to | EN 61010-2-201 |
| Rated voltage | 300 V |
| Pollution severity | 2 |
| Surge voltage category | III |
| Clearance and creepage distances for control side – load side | ≥ 6 mm |
| Dielectric strength for control side – load side | 3.51 kVeff /1 min. |
| Protection degree | IP20 |
| Standards | EN 61010-1 EN 61010-2-201 EN 61326-3-2 EN 61326-1 EN 61326-3-1 DIN EN 61508 |
| Certificate no. (cULus) | E141197 |
| Wire connection method | Screw connection |
| Stripping length, rated connection | 8 mm |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 1.5 mm² |
| Clamping range, min. | 0.13 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 26 |
| Wire connection cross section AWG, max. | AWG 12 |
| Wire cross-section, solid, min. | 0.2 mm² |
| Wire cross-section, solid, max. | 2.5 mm² |
| Wire connection cross section, finely stranded, min. | 0.2 mm² |
| Wire connection cross section, finely stranded, max. | 2.5 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. | 0.2 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. | 2.5 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), min. | 0.2 mm² |
| Conductor cross-section, flexible, AEH (DIN 46228-1), max. | 2.5 mm² |
| Blade size | size PH0 |
| Certificate No. (ATEX) | UL20ATEX2457X |
| Certificate No. (IECEX) | IECExULD20.0032X |
| Certificate no. (cULus) | E141197 |
| Certificate no. (cULusEX) | E324123 |
| Marking EN 60079 | Ex ec nC IIC T4 Gc |





Reviews