Weidmueller ACT20C-CMT-10-AO-RC-S

Request a price

ACT20C-CMT-10-AO-RC-S

SKU: 1510240000.0 Category: Brand:

Current-measuring transducer, Input : 0…5/10 A, Output : 0(4)-20 mA, 0-10 V, Relay

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 117.2 mm
Height (inches) 4.614 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 154 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…60 °C
Humidity 5…95 %, no condensation
SIL in compliance with IEC 61508 None
MTTF 130 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Input frequency AC: 15…700 Hz
Input measurement range configurable 0…5/10 A AC (RMS) or DC
Input signal Current-carrying cable in feed-through hole Diameter 10.5 mm
Interface Communication via CH20M rail bus with gateway (ACT20C-GTW-100-MTCP-S)
Load impedance current ≤ 600 Ω
Max. switching voltage, AC 250 V
Max. switching voltage, DC 24 V
Rated switching current 6 A
Type Relay, 1 CO contact Process alarms (4x) with hysteresis with alarm delay (configurable) 0…180 s
Load resistance current ≤ 600 Ω
Load resistance voltage ≥ 10 kΩ
Output current Adjustable 0…20 mA 4…20 mA -20…+20 mA
Output voltage Adjustable 0…10 V 2…10 V 0…5 V 1…5 V -5…+5 V -10…+10 V
Type (analogue output) Voltage and current output (configurable)
Switching current 5 A
Accuracy <0.75 % FSR
Configuration With FDT/DTM software via gateway (ACT20C-GTW-100-MTCP-S) Addressing via DIP switches
Nominal power consumption 3 VA
Power consumption, max. 2.2 W
Rail TS 35
Step response time <300 ms
Temperature coefficient typ. 0.04 % / K max. 0.09 % / K
Voltage supply via the system bus
EMC standards IEC 61326-1
Galvanic isolation 4-way isolator; between input ⁄ output ⁄ supply ⁄ relay
Impulse withstand voltage 6.4 kV (1.2/50 µs)
Pollution severity 2
Rated voltage 300 V ACrms
Surge voltage category III
Test voltage 4 kV
Type of connection Screw connection
Tightening torque, min. 0.5 Nm
Tightening torque, max. 3.5 Nm
Clamping range, rated connection 1.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, solid, max. 2.5 mm²
Product information The ACT20C-CMT-XX-AO-RC-S current measuring transducers from the ACT20C series measure and monitor DC and AC currents of up to 60 A. The True RMS method used allows for precise measurement, even in case of distorted current waveforms. The devices feature integrated limit value monitoring with an adjustable switching threshold, delay and hysteresis, as well as a relay output. Properties True RMS value measurement or arithmetic averaging (AA) measurement and contactless through-hole technologyLimit value monitoring for overcurrent or undercurrentRelay output by means of the open-circuit / closed-circuit principleInfinitely variable trigger delayOperational status and error display on a front panel LED and output signalling according to NE43, NE44, NE107Galvanic four-way insulation for secure isolation according to IEC/EN 61010-2-201:2013