Current-measuring transducer, Input : 0…40/50/60 A, Output : 0(4)-20 mA, 0-10 V, Relay
Technical Specifications:
| Depth | 113.6 mm |
| Depth (inches) | 4.472 inch |
| Height | 117.2 mm |
| Height (inches) | 4.614 inch |
| Width | 22.5 mm |
| Width (inches) | 0.886 inch |
| Net weight | 154 g |
| Storage temperature | -40 °C…85 °C |
| Operating temperature | -25 °C…60 °C |
| Humidity | 5…95 %, no condensation |
| SIL in compliance with IEC 61508 | None |
| MTTF | 130 a |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Input frequency | AC: 15…700 Hz |
| Input measurement range | configurable 0…40/50/60 A AC (RMS) or DC |
| Input signal | Current-carrying cable in feed-through hole Diameter 10.5 mm |
| Interface | Communication via CH20M rail bus with gateway (ACT20C-GTW-100-MTCP-S) |
| Load impedance current | ≤ 600 Ω |
| Max. switching voltage, AC | 250 V |
| Rated switching current | 6 A |
| Type | Relay, 1 CO contact Process alarms (4x) with hysteresis with alarm delay (configurable) 0…180 s |
| Load resistance current | ≤ 600 Ω |
| Load resistance voltage | ≥ 10 kΩ |
| Output current | Adjustable 0…20 mA 4…20 mA -20…+20 mA |
| Output voltage | Adjustable 0…10 V 2…10 V 0…5 V 1…5 V -5…+5 V -10…+10 V |
| Type (analogue output) | Voltage and current output (configurable) |
| Switching current | 5 A |
| Accuracy | <0.75 % FSR <1.5 % FSR with measurement range 50/60 A AC |
| Configuration | With FDT/DTM software via gateway (ACT20C-GTW-100-MTCP-S) Addressing via DIP switches |
| Nominal power consumption | 3 VA |
| Power consumption, max. | 2.2 W |
| Rail | TS 35 |
| Step response time | <300 ms |
| Temperature coefficient | typ. 0.04 % / K max. 0.09 % / K |
| Voltage supply | via the system bus |
| EMC standards | IEC 61326-1 |
| Galvanic isolation | 4-way isolator; between input ⁄ output ⁄ supply ⁄ relay |
| Impulse withstand voltage | 6.4 kV (1.2/50 µs) |
| Pollution severity | 2 |
| Rated voltage | 300 V ACrms |
| Surge voltage category | III |
| Test voltage | 4 kV |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.5 Nm |
| Tightening torque, max. | 3.5 Nm |
| Clamping range, rated connection | 1.5 mm² |
| Clamping range, min. | 0.5 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 30 |
| Wire connection cross section AWG, max. | AWG 14 |
| Wire cross-section, solid, min. | 0.5 mm² |
| Wire cross-section, solid, max. | 2.5 mm² |
| Product information | The ACT20C-CMT-XX-AO-RC-S current measuring transducers from the ACT20C series measure and monitor DC and AC currents of up to 60 A. The True RMS method used allows for precise measurement, even in case of distorted current waveforms. The devices feature integrated limit value monitoring with an adjustable switching threshold, delay and hysteresis, as well as a relay output. Properties True RMS value measurement or arithmetic averaging (AA) measurement and contactless through-hole technologyLimit value monitoring for overcurrent or undercurrentRelay output by means of the open-circuit / closed-circuit principleInfinitely variable trigger delayOperational status and error display on a front panel LED and output signalling according to NE43, NE44, NE107Galvanic four-way insulation for secure isolation according to IEC/EN 61010-2-201:2013 |