EX signal isolating converter, Ex-input: NAMUR sensor/switch, Safe-output: Optocoupler, 1-channel
Technical Specifications:
| Depth | 113.6 mm |
| Depth (inches) | 4.472 inch |
| Height | 119.2 mm |
| Height (inches) | 4.693 inch |
| Width | 22.5 mm |
| Width (inches) | 0.886 inch |
| Net weight | 170 g |
| Storage temperature | -20 °C…85 °C |
| Operating temperature | -20 °C…60 °C |
| Humidity | 0…95 % (no condensation) |
| SIL PAPER | SIL certificate |
| SIL in compliance with IEC 61508 | 2 |
| MTBF | 215 a |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Mounting position | horizontal or vertical |
| Rail | TS 35 |
| Type of mounting | Snap mounting support rail |
| Input frequency | 0…5 kHz |
| Input resistance | 1 kΩ |
| NAMUR supply | 8 V DC / 8 mA |
| Output signal in case of wire break | 6.5 mA (in case of wire break) |
| Pulse duration | > 0.1 ms |
| Resistance | Series resistor 750Ω Parallel resistor 15kΩ |
| Sensor | NAMUR sensor, according to EN60947-5-6 switch with or without RS, RP |
| Sensor supply | 8 V DC / 8 mA |
| Trigger level high | > 2.1 mA |
| Trigger level low | <1.2 mA |
| Type | intrinsically safe circuit |
| Continuous current | 80 mA |
| Function | Output = input direct or inverse (configurable) |
| Max. switching frequency | ≤ 5 kHz |
| Nominal switching voltage | 30 V DC |
| Type | NPN-Transitor |
| Alarm function | Line interruption at the input Short circuit at input No supply voltage Device error |
| Continuous current | ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2) |
| Nominal switching voltage | ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2) |
| Power rating | ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2) |
| Type | Status relay 1 NC (voltage-free) |
| Configuration | With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB |
| Humidity | 0…95 % (no condensation) |
| Operating altitude | ≤ 2000 m |
| Power consumption | ≤ 1.1 W |
| Protection degree | IP20 |
| Type of connection | Screw connection |
| Voltage supply | 19.2…31.2 V DC |
| EMC standards | EN 61326-1 |
| Insulation voltage | 2.6 kV (input / output) |
| Rated voltage | 300 V |
| Standards | EN 61010-1 |
| Current I0 | 12 mA DC |
| Installation location | Device installed in safe area, zone 2 |
| Marking | II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Power P0 | 32 mW |
| Voltage U0 | 10.6 V DC |
| Description of the “safe state” | High impedance |
| Device type | B |
| Diagnostic test interval | 10 s |
| Tproof | 5 a |
| Total failure rate for safe detected failures (λSD) | 0 FIT |
| Hardware fault tolerance (HFT) | 0 |
| Safety category | SIL 2 |
| Safe Failure Fraction (SFF) | 92 % |
| Mean Time To Repair (MTTR) | 8 h |
| Total failure rate for safe undetected failures (λSU) | 275 FIT |
| Total failure rate for dangerous detected failures (λDD) | 135 FIT |
| Total failure rate for dangerous undetected failures (λDU) | 36 FIT |
| Probability of outage PFH | 3.62 x 10-8 h-1 |
| Demand mode | High |
| Demand rate | 1,000 s |
| Average Probability of Failure on Demand (PFDavg) | 1.58 x 10-4 (Tproof = 1 year) 3.17 x 10-4 (Tproof = 2 years) 7.92 x 10-4 (Tproof = 5 years) |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.25 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 26 |
| Wire connection cross section AWG, max. | AWG 12 |
| Time interval | 3 years |
| Long specification | Ex isolating switch amplifiers for Namur sensors,1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is an NPN switching transistor and a common alarm contact (relay/”a” contact) for status or error messages.The component can be configured using standard FDT/DTM software.Add-on housing for TS35 DIN rail installationDimensions: L/W/H 119.2/ 22.5/ 113.6screw connection/ nominal cross-section 2.5 mm2Protection degree: IP20 Input NAMUR sensor according to EN 60947 8 VDC / 8 mA sensor power supply 0 to 5 kHz input frequency wire-break detectionOutput NPN transistor 30 VDC @ 80 mA 5 kHz switching frequency < 2, 5 VDC SpannungsfallAlarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2Auxiliary power 19…31.2 VDCPower loss approx. 1.8 WAmbienttemperature range -20 °C to +60 °CSecure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G ExnA nC IIC T4 ATEX characteristic data U0 = 10, 6 V DC I0 = 12 mA DC P0 = 32 WType ACT20X-HDI-2SDO-2SDO-S |
| Short specification | Ex isolating switch amplifiers for Namur sensors,1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1, 2 into the safe zone. On the output side there is an NPN switching transistor and a common alarm contact (relay/”a” contact) for status or error messages.The component can be configured using standard FDT/DTM software. |





Reviews
There are no reviews yet.