Weidmueller ACT20X-SDI-HDO-H-S

Request a price

ACT20X-SDI-HDO-H-S

SKU: 8965410000.0 Category: Brand:

EX signal isolating converter, Safe-input: relay, Ex-output: Opto module, High-current, 1-channel, Output current : max. 60 mA

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 119.2 mm
Height (inches) 4.693 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 170 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL PAPER SIL certificate
SIL in compliance with IEC 61508 2
MTBF 175 a
SFF 91 %
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting Rail Snap mounting support rail
Input resistance, voltage 3.5 kΩ
Input voltage ≤ 28 V DC Trigger level low: ≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP) Trigger level high: ≥ 4.0 V DC (NPN), ≥ 10.0 V DC (PNP)
Number of inputs 1
Type NPN, PNP transistor, switching signal [input safe-side valve component]
Output current max. 60 mA
Output values Current: max.: 60 mA Voltage: min.: 9 V Current: max.: 50 mA Voltage: min.: 11.5 V Current: max.: 60 mA Voltage: min.: 10 V Current: max.: 50 mA Voltage: min.: 12.5 V Current: max.: 60 mA Voltage: min.: 11 V Current: max.: 50 mA Voltage: min.: 13.5 V
Output values depending on terminal assignment: 9 V @ 60 mA / 11.5 V @ 50 mA / 10 V @ 60 mA / 12.5 V @ 50 mA / 11 V @ 60 mA / 13.5 V @ 50 mA
Output values depending on terminal assignment
Residual ripple (current loop) <40 mVeff
Type intrinsically safe circuit digital, output = input direct or inverse (configurable)
Max. switching frequency 20 Hz
Alarm function No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Status relay 1 NC (voltage-free)
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤ 2.5 W
Protection degree IP20
Step response time 10 ms
Type of connection Screw connection
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 ≤ 135 mA
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Power P0 ≤ 0.77 W
Voltage U0 28 V DC
Description of the “safe state” de-energized (relay output)
Device type B
Diagnostic test interval 10 s
Tproof 4 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Safe Failure Fraction (SFF) 91 %
Mean Time To Repair (MTTR) 24 h
Total failure rate for safe undetected failures (λSU) 480 FIT
Total failure rate for dangerous detected failures (λDD) 61 FIT
Total failure rate for dangerous undetected failures (λDU) 46 FIT
Probability of outage PFH 4.6 x 10-8 h-1
Demand mode High
Demand rate 1,000 s
Demand response time <10 ms (opto output)
Average Probability of Failure on Demand (PFDavg) 2.92 x 10-4 (Tproof = 1 year) 4.84 x 10-4 (Tproof = 2 year) 1.06 x 10-4 (Tproof = 5 year)
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.25 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 12
Time interval 3 years
Long specification Ex valve control modules, 60 mA ignition protection group IIB 1-channel valve control modules in 22.5 mm width with external power supply, to control valves in Ex areas zone 0,1,2 from the safe zone. The module comes with full three-way, 2.6 kV separation. On the input side, NPN/PNP switching sensors can be connected. On the output side, there are three 60 mA driver steps for ignition protection group IIB with a minimum driver voltage of 9 V/11 V or 12.5 V available optionally. An additional alarm contact (“a” contact) reports status and error messages The module can be configured using standard FDT/DTM software. Add-on housing for TS35 DIN rail installation Dimensions: L/W/H 119.2/ 22.5/ 113.6Screw connection/ nominal cross-section 2.5 mm2Protection degree: IP20 input NPN, PNP switch signal max. 28 VDC output Ex Imax 60 mA @ ignition protection group IIB U with load min. 9 V / min. 11 V / min. 12.5 V U without load min. 24 V Alarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A / 32 VDC @ 1 A zone 2Auxiliary power 19 to 31.2 VDCPower loss approx. 1.8 W Ambienttemperature range -20 °C to +60 °C Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2 Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G Ex nA nC IIC T4 ATEX characteristic data U0 = 28 V DC I0 = 125 mA P0 = 0.77 W Type ACT20X-SDI-HDO-H-S
Short specification Ex valve control modules, 60 mA ignition protection group IIB1-channel valve control modules in 22.5 mm width with external power supply,to control valves in Ex zones 0,1,2 from the safe zone. The module comes with full three-way, 2.6 kV separation. On the input side, NPN/PNP switching sensors can be connected. On the output side, there are three 60 mA driver steps for ignition protection group IIB witha minimum driver voltage of 9 V/11 V or 12.5 V available optionally. An additional alarm contact (“a” contact) reports status and error messagesThe module can be configured using standard FDT/DTM software.

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20X-SDI-HDO-H-S”