Weidmueller ACT20X-HUI-SAO-P

Request a price

ACT20X-HUI-SAO-P

SKU: 2456200000.0 Category: Brand:

EX signal isolating converter, Ex-output: U, I, R,ϑ, Safe-output: 4-20mA/ relay, 1-channel

Technical Specifications:

Depth 114.6 mm
Depth (inches) 4.512 inch
Height 127.3 mm
Height (inches) 5.012 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 202 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL PAPER SIL certificate
SIL in compliance with IEC 61508 2
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting DIN rail
Input current 0…20 mA 4…20 mA
Input resistance configurable 0…10 kΩ
Input resistance, current 20 Ω + PTC 50 Ω
Input resistance, voltage > 10 MΩ @ 600 mV 2 MΩ @ 28 V
Input voltage configurable 0…1 V DC 0,2…1 V DC 1…5 V DC 0…(5)10 V 2…10 V DC
Line resistance in measuring circuit ≤ 50 Ω
Potentiometer 10 Ω…10 kΩ
Sensor 2-/3-/4-wire RTD: PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000 Thermocouples: B, E, J, K, N, R, S, T ; in compliance with IEC 60584-1 and L, U in compliance with DIN43710 Potentiometer Resistance: 0 – 12 kΩ
Sensor supply 21.4…16.5 V DC / 0…20 mA
Temperature input range Configurable PT100: -200…+850 °C K: (-180…+1372 °C) L: (-200…+900 °C) N: (-180…+1300 °C) R: (-50…+1760 °C) S: (-50…+1760 °C) T: (-200…+400 °C) U: (-200…+600 °C) W3: (0…+2300 °C) W5: (0…+2300 °C) LR: (-200…+800 °C) PT200: -200…+850 °C PT1000: -200…+850 °C NI100: -60°C…+250 °C Ni120: -80 °C…+320 °C NI1000: -60°C…+250 °C B: +100…+1820 °C E: (-100…+1000 °C) J: (-100…+1200 °C)
Type intrinsically safe circuit
Load impedance current ≤ 600 Ω
Output current 0…23 mA, configurable: 0…20 / 4…20 / 20…0 / 20…4 mA configurable downscale (3.5 mA) ⁄ upscale (23 mA) @ error
Output signal limit 3.8…20.5 mA / 0…20.5 mA (dependent on range)
Type active (as current source) or passive (as current sink)
Continuous current ≤ 2 A AC/DC (safe area, Zone 2 area)
Function Configurable switching thresholds Window function Sensor error
Max. switching frequency 20 Hz
Nominal switching voltage ≤ 250 V AC / 30 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 500 VA / 60 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Relay, 1 NO / NC contact
Alarm function Short circuit at input Open circuit at input No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Status relay 1 NC (voltage-free)
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤ 2.1 W
Protection degree IP20
Type of connection PUSH IN
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 18.4 mA
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA I (M1) [Ex ia Ma] I II (1) G [Ex ia Ga] IIC II (1) D [Ex ia Da] IIIC
Power P0 40 mW
Voltage U0 8.7 V DC
Description of the “safe state” analogue Output ≤ 3.6 mA or output ≥ 21 mA de-energized (relay output)
Device type B
Diagnostic test interval 30 s
Tproof 4 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Relay lifetime 100000 times
Safe Failure Fraction (SFF) 93 %
Mean Time To Repair (MTTR) 24 h
Total failure rate for safe undetected failures (λSU) 278 FIT
Total failure rate for dangerous detected failures (λDD) 352 FIT
Total failure rate for dangerous undetected failures (λDU) 43 FIT
Probability of outage PFH 4.33 x 10-8 h-1
Demand mode High
Demand rate 3,000 s
Demand response time Signal input: <0.5 s (opto output) Temperature input: <1.1 s (opto output)
Average Probability of Failure on Demand (PFDavg) 2.82 x 10-4 (Tproof = 1 year) 4.63 x 10-4 (Tproof = 2 years) 1.00 x 10-3 (Tproof = 5 years) additional data in the safety manual
Type of connection PUSH IN
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Time interval 3 years

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20X-HUI-SAO-P”

Your email address will not be published. Required fields are marked *