Display, Input : I/U universal, Temperature, Output : Display, analogue V / mA, 4 x Relay
Technical Specifications:
| Depth | 120 mm |
| Depth (inches) | 4.724 inch |
| Height | 48.8 mm |
| Height (inches) | 1.921 inch |
| Width | 96.6 mm |
| Width (inches) | 3.803 inch |
| Net weight | 315 g |
| Operating temperature | -20 °C…60 °C |
| Humidity | 5…95 % rel. humidity, no condensation |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 6c, 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 Potassium perfluorobutane sulfonate 29420-49-3 |
| SCIP | f4905d12-f516-4eb5-90a8-8c87685bc956 |
| Cycle time | 2.2 times / s |
| Decimal point | 18888, 1.8888, 18.888, 188.88, 1888.8 |
| Dimmable | Yes |
| Display range | -1999…9999 |
| Display value | current measured value Percentage or real value display Switching status |
| Format | 14 segment (numbers + letters) Scrolling text in 8 languages in case of error (e.g. sensor wire breakage, input overrange…) |
| Scaling | Variable |
| Type | red LED 4-character display Digit size: 13.8 mm |
| Accuracy | <0.1 % of measuring range |
| Configuration | Front push-button |
| DIN Rail compatibility | No |
| Power consumption | ≤ 3.5 W |
| Protection degree | IP20 IP65 (in plugged condition) IP65 |
| Temperature coefficient | ≤0,01% of measurement range⁄°C |
| Type of connection | Tension clamp connection with actuator |
| Type of mounting | Frontpanel mounting Front mounting |
| Voltage supply | 21.6…253 VAC, (50…60 Hz) or 19.2…300 VDC |
| cold junction compensation | internal |
| Input current | 0…20 mA 4…20 mA |
| Input resistance | 20 Ω |
| Input resistance, voltage | > 10 MΩ |
| Input voltage | 0…1 V DC 0,2…1 V DC 0…10 V DC 2…10 V DC |
| Line resistance in measuring circuit | 50 Ω |
| Number of inputs | 1 |
| Potentiometer | 10 Ω…10 kΩ |
| Response time | configurable 0.4…60 s (mA / V input) configurable 1…60 s (temperature input) |
| Sensor | 2-wire transmitter (without own power supply) 4- wire sensor (with own power supply) RTD (2,3-wire): Pt100, Pt200, Pt1000, Ni120, Cu10 Thermocouples: B / C / E / J / K / L / N / R / S / T / W3 / W5 Resistance measurement Potentiometer: 10 Ω…10 kΩ |
| Sensor supply | > 15 V DC at 20 mA |
| Temperature input range | E: (-100…+1000 °C) J: (-100…+1200 °C) W5: (0…+2300 °C) LR: (-200…+800 °C) PT100 / 200 / 1000: -200 °C…+850 °C K: (-180…+1372 °C) L: (-200…+900 °C) N: -180…+1300 °C R: (-50…+1760 °C) S: (-50…+1760 °C) T: (-200…+400 °C) U: (-200…+600 °C) W3: (0…+2300 °C) |
| Type | ‘active’,’connected control must be passive’ |
| Alarm function | Under voltage Over voltage Under-current Surge current Surge voltage Under-temperature Over-temperature Sensor error |
| Hysteresis | 0…100 % |
| Max. switching voltage, AC | 250 V |
| Max. switching voltage, DC | 30 V |
| Number of digital outputs | 4 |
| Rated switching current | 2 A |
| Rated switching voltage | 24…250 V AC |
| Switch-off delay | 0…3600 s |
| Switch-on delay | 0…3600 s |
| Switching capacity | 500 VA |
| Switching thresholds | 10…100% of %*UN |
| Type | 4 x 1 CO contact (hard gold-plated) |
| Type of switch function | direct or inverted |
| Load resistance current | ≤ 800 Ω |
| Number of analogue outputs | 1 |
| Output behaviour on failure downscale | 3.5 mA |
| Output behaviour on failure upscale | 23 mA |
| Signal output | direct or inverted |
| Type (analogue output) | ‘active’,’connected control must be passive’ |
| EMC standards | EN 61326-1 |
| Galvanic isolation | between input ⁄ output ⁄ supply ⁄ relay |
| Insulation voltage | 2.3 kVAC (Test) / 250 VAC (operating state) |
| Pollution severity | 2 |
| Wire connection method | Clamping yoke pluggable |
| Type of connection | Tension clamp connection with actuator |
| Wire connection cross section AWG, min. | AWG 30 |
| Wire connection cross section AWG, max. | AWG 12 |
| Wire connection cross section, finely stranded, min. | 0.13 mm² |
| Wire connection cross section, finely stranded, max. | 2.8 mm² |
| Product information | The device is a built-in device used to digitally display process values such as current, voltage, resistance, temperature and potentiometer signals in real-time. The device is designed for switch panel installation in a visible area. The device may only be used indoors. |





Reviews