Weidmueller CP DC UPS 24V 20A/10A

Request a price

CP DC UPS 24V 20A/10A

SKU: 1370050010.0 Category: Brand:

UPS control unit

Technical Specifications:

Depth 150 mm
Depth (inches) 5.905 inch
Height 130 mm
Height (inches) 5.118 inch
Width 66 mm
Width (inches) 2.598 inch
Net weight 1,139 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity 5…95 %, no condensation
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP d6c68c9e-3e33-4fa9-920e-331473bf0422
Parallel connection option yes, max. 2
Rated voltage 24 V
Storage medium 1.3 Ah 3.4 Ah 7.2 Ah 12 Ah 17 Ah Selectable with rotary switch
Battery availability test every minute
Charging current 0.15 cA
Charging feature IU characteristic curve
Charging voltage (temperature compensated) 27, 48 V @ 20°C
Temperature coefficient – 48 mV / °C
Function DIP switch Inversion of transistor outputs Operation without temperature probe
Output current selector switch 20 A 10 A
Remote disconnection (Interlock) Yes
Selector switch battery 1.3 Ah 3.4 Ah 7.2 Ah 12 Ah 17 Ah No Battery Service
Selector switch buffer times 0.5 min 1 min 3 min 5 min 10 min 20 min 30 min 45 min ∞ ∞ w/0
Temperature probe NTC 100 kΩ
DC current consumption max. 200 mA (without battery) max. 0.5 A (with fully charged battery)
DC input voltage range 20…30 V DC
Input current ≤ 13A (for 10A) ≤ 23A (for 20A)
Input fuse (internal) Yes
Max. approved input current 28 A
Rated input voltage 24 V DC
Wire connection method Screw connection
Continuous output current @ UNominal 24 A @ 45 °C 20 A @ 60 °C 15 A @ 70 °C
Nominal output current for Unom 20 A @ 60 °C
Output current, max. 24 A
Output voltage, note Vo = Vin – 0.2 V normal operation (Imax) Vo = Vin – 0.3 V battery supply (I max)
Overload protection Yes
Parallel connection option yes, max. 2 Yes, with diode module
Protection against inverse voltage Yes
Rated output voltage 24 V DC ± 1 %
Residual ripple, breaking spikes < 50 mVPP @ 24 V DC, IN
Temperature coefficient – 48 mV / °C
Temperature probe NTC 100 kΩ
Wire connection method Screw connection
Buffer times Depending on the connected battery
Clip-in foot metal
Current limiting > 120% IN
Degree of efficiency ≥ 96% normal mode, battery is being charged ≥ 98% normal mode, battery is charged ≥ 98% buffer mode
Housing version Metal, corrosion resistant
Humidity 5…95 %, no condensation
Mounting position, installation notice Horizontal on TS35 mounting rail. 50 mm of clearance at top & bottom for air circ. Can mount side by side with no space in between.
MTBF According to Standard: SN 29500 Operating time (hours), min.: 1,860,000 h Ambient temperature: 25 °C Input voltage: 24 V Output power: 240 W Duty cycle: 100 % According to Standard: SN 29500 Operating time (hours), min.: 906,400 h Ambient temperature: 40 °C Input voltage: 24 V Output power: 240 W Duty cycle: 100 %
Power loss < 10 W
Protection against reverse voltages from the load 32…34 V DC
Protection degree IP20
Short-circuit protection Yes
Storage medium 1.3 Ah 3.4 Ah 7.2 Ah 12 Ah 17 Ah Selectable with rotary switch
Surge voltage category III
Interference immunity test acc. to EN 61000-4-2 (ESD)EN 61000-4-3 and EN 61000-4-8 (fields)EN 61000-4-4 (burst)EN 61000-4-5 (surge)EN 61000-4-6 (conducted)EN 61000-4-11 (dips)
Noise emission in accordance with EN55032 Class B
Shock resistance IEC 60068-2-27 30 g in all directions
Vibration resistance IEC 60068-2-6 2.3 g
electrical isolation, input-earth 1 kV
electrical isolation, output-earth 1 kV
Insulation voltage 1 kV DC
Pollution severity 2
Protection class III, with no ground connection, for SELV
Surge voltage category III
Electrical machine equipment Acc. to EN60204
For use with electronic equipment Acc. to EN50178 / VDE0160
Protection against dangerous shock currents Acc. to VDE0106-101
Protective separation / protection against electrical shock VDE0100-410 / acc. to DIN57100-410
Safety transformers for switch-mode power supplies According to EN 61558-2-16
Conductor cross-section, AWG/kcmil , max. 6
Conductor cross-section, AWG/kcmil , min. 26
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 16 mm²
Conductor cross-section, rigid , min. 0.5 mm²
Reverse polarity protection Yes
Tightening torque, max. 1.5 Nm
Tightening torque, min. 1.2 Nm
Wire connection cross section, flexible (input), max. 16 mm²
Conductor cross-section, AWG/kcmil , max. 6
Conductor cross-section, AWG/kcmil , min. 26
Conductor cross-section, flexible , max. 16 mm²
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 16 mm²
Conductor cross-section, rigid , min. 0.6 mm²
Reverse polarity protection Yes
Tightening torque, max. 1.5 Nm
Tightening torque, min. 1.2 Nm
Wire connection cross-section, flexible (signal), max. 1.5 mm²
Wire connection cross-section, flexible (signal), min. 0.2 mm²
Wire connection method Screw connection
Wire cross-section, AWG/kcmil , max. 15
Wire cross-section, AWG/kcmil , min. 30
Wire cross-section, solid , max. 1.5 mm²
Wire cross-section, solid , min. 0.2 mm²
Floating contact Yes
Status indicator Three-colour LED: Battery capacity >85% green, >40% yellow, >20% red, <20% red (Flashing) Green/yellow LED: normal / buffering Yellow/red LED: temperature alarm / alarm Yellow/red LED: switch-off / battery fault
Status relay (max. load) Fault (alarm) (30 V AC/DC 0.1 A) Battery operation (buff.) (30 V AC/DC 0.1 A) Laden (Charg.) (30V AC/DC 0,1A)
Transistor outputs (24&…27 V DC max. load 150 mA) Battery operation (buff.) Charging Fault (alarm)

Reviews

There are no reviews yet.

Be the first to review “Weidmueller CP DC UPS 24V 20A/10A”

Your email address will not be published. Required fields are marked *