Weidmueller ACT20P-UI-2RCO-AC-S

Request a price

ACT20P-UI-2RCO-AC-S

SKU: 1238910000.0 Category: Brand:

Limit value monitoring, Input : universal U, I, R,ϑ, Output : 2 x relays, 90…264 V AC power supply

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 119.2 mm
Height (inches) 4.693 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 345.685 g
Storage temperature -20 °C…70 °C
Operating temperature -20 °C…60 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 10…90 %, no condensation
SIL in compliance with IEC 61508 None
MTBF 180 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Cable-length compensation <±0.002 Ω per cable resistance Ω
Influence of the sensor cable resistance 5 Ω @ RTD- Kabel
Input current configurable ± 25 mA DC ±5 A DC
Input resistance, current 40 Ω
Input resistance, voltage 2 MΩ > 10 MΩ
Input voltage configurable ±150 mV DC ± 600mV DC ±30 V DC ±300 V DC
Number of inputs 1
Potentiometer 1.2…500 kΩ
Resistance 0…10 kΩ 0…12 kΩ 0…15 kΩ
Sensor RTD (2,3-wire): Pt100, Pt200, Pt1000, Ni120, Cu10 Thermocouples: B, E, J, K, L, N, R, S, T,U
Sensor supply 0.1 mA / 0.05 mA (depending on measuring range) @ RTD cable 24 V (@ 4-20 mA loop)
Temperature input range B: +100…+1820 °C E: -270…+1000 °C J: (-210…+1200 °C) K: -270…+1372 °C L: +100…+900 °C N: (-180…+1300 °C) R: -50…+1768 °C S: -50…+1768 °C T: -270…+400 °C U: -200…+600 °C
Number of outputs 2
Alarm function configurable Top and bottom limit values, window range Alarm delay: 0…99 s Hysteresis adjustable auto / manual reset
Max. switching voltage, AC 250 V
Max. switching voltage, DC 110 V
Number of digital outputs 2
Rated switching current 200mA @ 110Vdc 6A @ 24Vdc / 240Vac
Type 2 CO contacts normal / inverse adjustment Switching frequency 20 Hz
Accuracy <0.1 % of measuring range
Cold-junction compensation error ±2.0°C @ -20° C – 70°C
Configuration With FDT/DTM software or via 7-segment display, push-buttons and rotary encoder on the device itself Requires configuration adapter 8978580000 CBX200 USB
Long-term drift 0.1 % / 10.000 h
Nominal power consumption 1.5 VA
Operating altitude ≤ 2000 m
Power consumption ≤ 3.5 W <2 W
Protection degree IP20
Rail TS 35
Repeat accuracy ± 0.05 % of measuring range final value
Step response time 450 ms
Temperature coefficient <0.02 °C of measuring range / °C 350 ppm/K
Voltage supply 90…264 V AC
EMC standards EN 61326-1
Galvanic isolation between input ⁄ output ⁄ supply ⁄ relay
Impulse withstand voltage 4 kV (1.2/50 µs)
Insulation voltage 4 kV (input / output)
Pollution severity 2
Rated voltage 300 Veff
Surge voltage category III
Test voltage 0.3 kV
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 12
Product information The devices of the ACT20P-UI-2RCO-XX-x family record current, voltage, potentiometer and temperature sensor signals (mA, A, mV, V, potentiometer, RTD and TC). They have two independent relay outputs which emit an alarm when levels exceed or fall below pre-set limits. Properties Configuration and diagnosis with the FDT/DTM software “WI-Manager”. Manual configuration on the device is performed via the LED display by means of operating buttons and rotary encoders. The dual-channel trip amplifier enables various alarm functions: window alarm, alarm delay, wire break detection, hysteresis and upper / lower limit alarm. The active or passive signal inputs for RTD, TC, potentiometer, voltage and current are fully galvanically isolated. Remote diagnosis: reporting of errors (e.g. cable breaks) via status relay. Operational status and relay status indicated by front panel LEDs. Galvanic 4-way isolation between input, output and supply.
Long specification Universal limit-value monitoring component with relay output andexternal supplyUniversal limit-value monitoring component in 22.5 mm width with external voltage and sensor supply, for monitoring and isolating DC currents +/- 25mA…5 A,DC voltages +/-600 mV… 300 V, 2-/3-/-4-wire RTD sensors , resistors, potentiometersand thermocouple signals according to IEC584.Two relay contacts (CO) are available on the output side.This component is programmed using FDT/DTM software.Add-on housing for TS35 rail mountingDimensions: L/W/H 119/ 22.5/ 113.6 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input +/-25 mA…5 A DC +/- 600 mV…300 V DC PT100, PT1000, Ni100, Ni1000 Resistance 0…12 kOhm Potentiometer 0…500 kOhm Thermocouple types B, E, J, K, L, LR, N, R, S, T, U, W3, W5Sensor supply 24 V DC Output 2 x 1 CO (hard gold-plated) 240 V AC/ 24 V DC @ 6 ARepeat accuracy < 0,05 % v. E. Step response time10…90 % < 200 msAuxiliary power 90…264 V AC / 120…370 V DCPower loss approx. 3 W @ 240 V ACAmbient temperature range -20 °C…+70 °CIsolation EN 50178 secure 3-way isolation up to 3 kV AC/DC of all circuits against each otherTest voltage 3 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULusType ACT20P-UI-2RCO-AC-S
Short specification Universal limit-value monitoring component with relay output and external supplyUniversal limit-value monitoring component in 22.5 mm width with external voltage and sensor supply for monitoring and isolating DC currents +/- 25mA…5 A, DC- voltages +/-600 mV… 300 V, 2-/3-/-4-wire RTD sensors, resistors, potentiometers and thermocouple signals, in compliance with IEC584. Two relay contacts (CO) are available on the output side. This component is programmed using FDT/DTM software.

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20P-UI-2RCO-AC-S”

Your email address will not be published. Required fields are marked *