Weidmueller TRPL 48-110VDC 1NO TRAK

Request a price

TRPL 48-110VDC 1NO TRAK

SKU: 2774020000.0 Category: Brand:

TERMSERIES-compact, Relay module, Number of contacts: 1, NO contact AgSnO2, Rated control voltage: 48 V…110 V DC +25 % / -30 %, Continuous current: 6 A, PUSH IN, Test button available: No

Technical Specifications:

Depth 62.5 mm
Depth (inches) 2.461 inch
Height 89.4 mm
Height (inches) 3.52 inch
Width 6.4 mm
Width (inches) 0.252 inch
Net weight 25 g
Storage temperature -40 °C…85 °C
Operating temperature -40 °C…70 °C
Humidity 95 % for 30 days, minimal condensation to EN 50155
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 75e5f661-708e-44b0-9fc2-4f6c675b3b71
Rated control voltage 48 V…110 V DC +25 % / -30 %
Rated current DC 2.4 mA @ 48 V DC 3.2 mA @ 110 V DC
Power rating 115 mW @ 48 V DC 352 mW @ 110 V DC
Coil resistance 10600 Ω ± 15 %
Status indicator Green LED
Protective circuit Suppressor diode Free-wheeling diode
Rated switching voltage 250 V AC
Continuous current 6 A
Max. switching frequency at rated load 0.1 Hz
Max. switching voltage, AC 250 V
Max. switching voltage, DC 250 V
Min. switching power 1 mA @ 24 V 10 mA @ 12 V 100 mA @ 5 V
Inrush current 20 A / 20 ms
AC switching capacity (resistive), max. 1500 VA
Switch-on delay <11 ms
Switch-off delay <30 ms
Contact type 1 NO contact (AgSnO2)
Mechanical service life 10 x 106 switching cycles
Operating altitude ≤ 2000 m above sea level
Version for railway applications
Rail TS 35
Test button available No
Mechanical switch position indicator No
Colour black
UL94 flammability rating component Component: Housing UL94 flammability rating: V-0 Component: Relay status indicator UL94 flammability rating: V-0 Component: Pusher UL94 flammability rating: V-0
Rated voltage 300 V
Pollution severity 2
Surge voltage category III
Clearance and creepage distances for control side – load side ≥ 6 mm
Dielectric strength for control side – load side 2.5 kVeff
Type of isolation at input and output reinforced insulation
Dielectric strength of open contact 1 kVeff / 1 min
Dielectric strength to mounting rail 4 kVeff / 1 Min.
Impulse withstand voltage 6 kV (1.2/50 µs)
Protection degree IP20
Wire connection method PUSH IN
Stripping length, rated connection 9 mm
Clamping range, rated connection 1.5 mm²
Clamping range, min. 0.14 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.5 mm²
Wire cross-section, solid, max. 1.5 mm²
Wire cross-section, solid, min. (AWG) AWG 26
Wire cross-section, solid, max. (AWG) AWG 14
Wire connection cross section, finely stranded, min. 0.35 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire cross-section, finely stranded, min. (AWG) AWG 26
Wire cross-section, finely stranded, max. (AWG) AWG 14
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.14 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 1.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min. 0.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 1.5 mm²
Blade size 0.6 x 3.5 mm