Weidmueller ACT20M-BAI-2AO-S

Request a price

ACT20M-BAI-2AO-S

SKU: 1375470000.0 Category: Brand:

Signal splitter, Configurable, Input : I/U/bidirectional I, Output : 2 x I/U or 1 x bidirectional

Technical Specifications:

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 80 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation
SIL in compliance with IEC 61508 None
MTBF 181 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Input current configurable -10 mA…0…+10 mA -20 mA…0…+20 mA
Input resistance, voltage ≥ 1 MΩ
Input voltage configurable -5 V…0…+5 V -10 V…0…+10 V
Number of inputs 1
Sensor Voltage source Current source
Voltage drop, current input 1 V at 20 mA
Cut-off frequency (-3 dB) ≥ 100 Hz 10 Hz
Load impedance current <300 Ω per channel
load impedance voltage ≥ 10 kΩ
Number of outputs 2
Output current configurable 0…20 mA 4…20 mA 1 channel -10…0…+10 mA 1 channel -20…0…+20 mA
Output voltage, note configurable 0(2)…10 V 0(1)…5 V
Type active connected control must be passive
Accuracy <0.05 % of measuring range
Configuration DIP switch
Delivery state Setting parameters: Bandwidth Configuration: 100 Hz Setting parameters: Input Configuration: -10…10 V Setting parameters: Output 1 Configuration: 0…20 mA Setting parameters: Output 2 Configuration: 0…20 mA
Delivery state Bandwidth: 100 Hz // Input: -10…10 V // Output 1: 0…20 mA // Output 2: 0…20 mA
Nominal power consumption 1.2 VA
Operating altitude ≤ 2000 m
Power consumption, max. 1.2 W
Power consumption, typ. 0.84 W
Protection degree IP20
Rail TS 35
Step response time ≤ 7 ms
Temperature coefficient <0.01% of span/°C (TU)
Voltage supply 24 V DC ±30 % at terminal or via CH20M rail bus
EMC standards EN 61326-1
Galvanic isolation 4-way isolator;
Insulation voltage 2.5 kVeff /1 min.
Pollution severity 2
Rated voltage 300 Veff
Surge voltage category II
Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
EMC standards EN 61326-1
Standards IEC 61010-1
Product information The configurable DC-Converter ACT20M-BAI-AO-S separates and converts standard analogue signals. An analogue input signal is converted linear and galvanic isolated into an analogue output signal. The power supply is galvanically isolated from input and output and happens via a direct wiring or the Weidmüller DIN Rail Bus (3-way isolation).The configurable DC-Converter ACT20M-BAI-2AO-S provides the same functionality, but has two galvanically separated outputs (4-way split).