Passive isolator, Input : 0(4)-20 mA, (loop powered), Output : 0(4)-20 mA, Input current loop feed
Technical Specifications:
| Depth | 114 mm |
| Depth (inches) | 4.488 inch |
| Height | 117.2 mm |
| Height (inches) | 4.614 inch |
| Width | 12.5 mm |
| Width (inches) | 0.492 inch |
| Net weight | 100 g |
| Storage temperature | -40 °C…85 °C |
| Operating temperature | -20 °C…60 °C |
| Humidity at operating temperature | 0…95 % (no condensation) |
| Humidity | 5…95 %, no condensation |
| SIL in compliance with IEC 61508 | None |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Input current | 0(4)…20 mA current loop |
| Number of inputs | 1 |
| Sensor | 4- wire sensor (with own power supply) Current source |
| Voltage drop, current input | 3.8 V |
| Load impedance current | ≤ 600 Ω |
| Number of outputs | 1 |
| Output current | 0…20 mA (if input: 0…20 mA) 4…20 mA (if input: 4…20 mA) |
| Type | active connected control must be passive |
| Max. switching voltage, AC | 0 V |
| Max. switching voltage, DC | 0 V |
| Rated switching current | 0.1 A |
| Accuracy | <0.1 % of end value |
| Configuration | none |
| Nominal power consumption | 2 VA |
| Operating altitude | ≤ 2000 m |
| Protection degree | IP20 |
| Rail | TS 35 |
| Step response time | ≤ 1 ms |
| Temperature coefficient | ≤ 100 ppm/K |
| Voltage supply | Loop powered, via 4…20 mA input |
| EMC standards | EN 61326-1 EN 61000-6-2 EN 61000-6-4 |
| Galvanic isolation | 2-way isolator |
| Impulse withstand voltage | 3 kV (1.2/50µs) |
| Insulation voltage | 2.5 kV (input / output) |
| Pollution severity | 2 |
| Rated voltage | 300 V |
| Surge voltage category | III |
| Marking | II 3 G Ex ec IIC T6 Gc |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.5 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 26 |
| Wire connection cross section AWG, max. | AWG 12 |
| Product information | The ACT20P-CI-CO-ILP-S fixed passive isolators isolate analogue standard current source signals. An analogue input current signal is converted linear and galvanic isolated into an analogue output current signal. The device is powered via the input current loop. Features Galvanic 2-way isolation (single-channel device) between input and output. |