Weidmueller ACT20P-CMT-30-AO-RC-P

Request a price

ACT20P-CMT-30-AO-RC-P

SKU: 1510320000.0 Category: Brand:

Current-measuring transducer, Limit value monitoring, Input : 0…20/25/30 A, Analogue output, Relay output, Current-carrying cable in feed-through hole

Technical Specifications:

Depth 114 mm
Depth (inches) 4.488 inch
Height 127.1 mm
Height (inches) 5.004 inch
Width 22.8 mm
Width (inches) 0.898 inch
Net weight 204 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…60 °C
Humidity 5…95 %, no condensation
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 6c, 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Input frequency AC: 15…700 Hz (true root mean square)
Input measurement range configurable 0…20/25/30 A AC (RMS) or DC max. peak current 10 × IInput (1 s) For DC current measurement (AA): Current direction display at the output (-/+ analog value)
Input signal Current-carrying cable in feed-through hole
Number of inputs 1
Overload behaviour Max. peak current: 10 × IInput for 1s
Type active connected control must be passive
Alarm function Surge current Under-current Alarm limit setting: 2 – 105 % Hysteresis 5% / 10% Alarm delay: 0…10 s
Continuous current 2 × I Input
Max. switching voltage, AC 250 V
Max. switching voltage, DC 24 V
Number of digital outputs 1
Rated switching current 6 A
Type Relay, 1 CO contact normal / inverse adjustment
Load resistance current ≤ 600 Ω
Load resistance voltage ≥ 10 kΩ
Number of analogue outputs 1
Output current Adjustable 0…20 mA 4…20 mA -20…+20 mA
Output voltage Adjustable 0…10 V 2…10 V 0…5 V 1…5 V -5…+5 V -10…+10 V
Transmit function direct or inverted
Accuracy <0.75 % FSR
Configuration DIP switch and potentiometer
Power consumption, max. 2.2 W
Power consumption, typ. 0.9 W
Protection degree IP20
Rail TS 35
Step response time ≤ 300 ms (RMS) ≤ 60 ms (AA)
Temperature coefficient typ. 0.04 % / K max. 0.09 % / K
Voltage supply 16,8 V…31,2 V
EMC standards EN 61326-1
Galvanic isolation 4-way isolator; between input ⁄ output ⁄ supply ⁄ relay
Impulse withstand voltage 6.4 kV (1.2/50 µs)
Insulation voltage 4 kVeff / 1 min.
Pollution severity 2
Rated voltage 300 V ACrms
Surge voltage category III
Test voltage 4 kV
Type of connection PUSH IN
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Product information The ACT20P-CMT-XX-(AO)-RC-P series of devices measure and monitor AC and DC currents of up to 60 A. The real effective value method used allows for precise measurement, even for distorted current curve shapes. The devices feature integrated limit value monitoring with an adjustable switching threshold, delay and hysteresis, as well as a relay output.. Features Real effective value measurement (True RMS) or arithmetic averaging (AA) measurement and contactless through-hole technology Limit value monitoring for overcurrent or undercurrent Relay output by means of the open-circuit / closed-circuit principle Adjustable trigger delay for filtering current peaks Operational status and error display on a front panel LED and output signalling according to NE43, NE44, NE107 Galvanic four-way insulation for secure isolation according to IEC/EN 61010-2-201