Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 119.2 mm
Height (inches) 4.693 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 158 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…60 °C
Humidity 5…95 %, no condensation
MTTF 100 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 6c, 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Input frequency AC: 15…700 Hz (true root mean square)
Input measurement range configurable 0…40/50/60 A AC (RMS) or DC max. peak current 10 × IInput (1 s) For DC current measurement (AA): Current direction display at the output (-/+ analog value)
Input signal Current-carrying cable in feed-through hole
Number of inputs 1
Overload behaviour Max. peak current: 10 × IInput for 1s
Alarm function Surge current Under-current Alarm delay: 0…10 s Hysteresis 5% / 10%
Continuous current 2 × I Input
Max. switching voltage, AC 250 V
Max. switching voltage, DC 24 V
Number of digital outputs 1
Rated switching current 6 A
Switching thresholds 2…105% of measurement range
Type Relay, 1 CO contact normal / inverse adjustment
Accuracy <0.75 % FSR <1.5 % FSR with measurement range 50/60 A AC
Configuration DIP switch and potentiometer
Power consumption, max. 2.2 W
Power consumption, typ. 0.9 W
Protection degree IP20
Rail TS 35
Step response time ≤ 300 ms (RMS) ≤ 60 ms (AA)
Temperature coefficient 0.01%/K @ 0…40 A 0.10%/K @ 40…55 A 0.30%/K @ 55…60 A
Voltage supply 16,8 V…31,2 V
EMC standards EN 61326-1
Galvanic isolation 3-way isolator between input ⁄ output ⁄ supply
Impulse withstand voltage 6.4 kV (1.2/50 µs)
Insulation voltage 4 kVeff / 1 min.
Pollution severity 2
Rated voltage 300 V AC eff
Surge voltage category III
Test voltage 4 kV
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 1.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 12
Product information The ACT20P-CMT-XX-(AO)-RC-S series of devices measure and monitor AC and DC currents of up to 60 A. The real effective value method used allows for precise measurement, even for distorted current curve shapes. The devices feature integrated limit value monitoring with an adjustable switching threshold, delay and hysteresis, as well as a relay output.. Features Real effective value measurement (True RMS) or arithmetic averaging (AA) measurement and contactless through-hole technology Limit value monitoring for overcurrent or undercurrent Relay output by means of the open-circuit / closed-circuit principle Adjustable trigger delay for filtering current peaks Operational status and error display on a front panel LED and output signalling according to NE43, NE44, NE107 Galvanic four-way insulation for secure isolation according to IEC/EN 61010-2-201