Weidmueller ACT20P-UI-2RCO-AC-P

Request a price

ACT20P-UI-2RCO-AC-P

SKU: 2495690000.0 Category: Brand:

Limit value monitoring, Input : universal U, I, R,ϑ, Output : 2 x relays, 90…264 V AC power supply

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 127.1 mm
Height (inches) 5.004 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 173 g
Operating temperature -20 °C…60 °C
Humidity at operating temperature 0…95 % (no condensation)
SIL in compliance with IEC 61508 None
MTBF 180 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Cable-length compensation <±0.002 Ω per cable resistance Ω
Influence of the sensor cable resistance 5 Ω @ RTD- Kabel
Input current configurable ± 25 mA DC ±5 A DC
Input resistance, current 40 Ω
Input resistance, voltage 2 MΩ > 10 MΩ
Input voltage configurable ±150 mV DC ± 600mV DC ±30 V DC ±300 V DC
Number of inputs 1
Potentiometer 1.2…500 kΩ
Resistance 0…10 kΩ 0…12 kΩ 0…15 kΩ
Sensor Thermocouples: B, E, J, K, L, N, R, S, T, U RTD: PT100, PT200, PT1000, Ni120, Cu10, 2-/3-/4-wire
Sensor supply 0.1 mA / 0.05 mA (depending on measuring range) @ RTD cable 24 V (@ 4-20 mA loop)
Temperature input range B: +100…+1820 °C E: -270…+1000 °C J: (-210…+1200 °C) K: -270…+1372 °C L: +100…+900 °C N: (-180…+1300 °C) R: -50…+1768 °C S: -50…+1768 °C T: -270…+400 °C U: -200…+600 °C
Number of outputs 2
Alarm function configurable Top and bottom limit values, window range Alarm delay: 0…99 s Hysteresis adjustable auto / manual reset
Max. switching voltage, AC 250 V
Max. switching voltage, DC 110 V
Number of digital outputs 2
Rated switching current 200mA @ 110Vdc 6A @ 24Vdc / 240Vac
Type 2 CO contacts normal / inverse adjustment Switching frequency 20 Hz
Configuration With FDT/DTM software or via 7-segment display, push-buttons and rotary encoder on the device itself Requires configuration adapter 8978580000 CBX200 USB
Long-term drift 0.1 % / 10.000 h
Nominal power consumption 1.5 VA
Operating altitude ≤ 2000 m
Power consumption <2 W
Protection degree IP20
Rail TS 35
Temperature coefficient <0.02 °C of measuring range / °C 350 ppm/K
Voltage supply 90…264 V AC
EMC standards EN 61326-1
Galvanic isolation between input ⁄ output ⁄ supply ⁄ relay
Type of connection PUSH IN
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Product information The devices of the ACT20P-UI-2RCO-XX-x family record current, voltage, potentiometer and temperature sensor signals (mA, A, mV, V, potentiometer, RTD and TC). They have two independent relay outputs which emit an alarm when levels exceed or fall below pre-set limits. Properties Configuration and diagnosis with the FDT/DTM software “WI-Manager”. Manual configuration on the device is performed via the LED display by means of operating buttons and rotary encoders. The dual-channel trip amplifier enables various alarm functions: window alarm, alarm delay, wire break detection, hysteresis and upper / lower limit alarm. The active or passive signal inputs for RTD, TC, potentiometer, voltage and current are fully galvanically isolated. Remote diagnosis: reporting of errors (e.g. cable breaks) via status relay. Operational status and relay status indicated by front panel LEDs. Galvanic 4-way isolation between input, output and supply.