EX signal isolating converter, HART® transparency, 2-channel, Safe-input: 4-20mA, Ex output: 4 – 20 mA
Technical Specifications:
| Depth | 113.6 mm |
| Depth (inches) | 4.472 inch |
| Height | 119.2 mm |
| Height (inches) | 4.693 inch |
| Width | 22.5 mm |
| Width (inches) | 0.886 inch |
| Net weight | 212 g |
| Storage temperature | -20 °C…85 °C |
| Operating temperature | -20 °C…60 °C |
| Humidity | 0…95 % (no condensation) |
| SIL PAPER | SIL certificate |
| SIL in compliance with IEC 61508 | 2 |
| MTBF | 135 a |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Mounting position | horizontal or vertical |
| Rail | TS 35 |
| Type of mounting | Snap mounting support rail |
| Input current | 4…20mA |
| Number of inputs | 2 |
| Voltage drop | <2 V |
| 2-wire supply | > 14.5 V @ 20 mA |
| Influence of load resistance | ≤ 0.01% of span / 100 Ω |
| Load impedance current | ≤ 725 Ω |
| Output current | 4…20 mA (max. 23 mA) |
| Output signal limit | <28 mA |
| Residual ripple (current loop) | <7.5 mVeff |
| Type | intrinsically safe circuit |
| Max. switching frequency | 0 Hz |
| Alarm function | Signal limit exceeded Line interruption at the input No supply voltage Device error |
| Continuous current | ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2) |
| Hysteresis | 0.1 mA (switching threshold) |
| Nominal switching voltage | ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2) |
| Power rating | ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2) |
| Switching thresholds | 0…29.9 mA (programmable) |
| Type | Status relay 1 NC (voltage-free) |
| Accuracy | <0.1% span |
| Configuration | With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB |
| HART® transparency supported | Yes |
| Humidity | 0…95 % (no condensation) |
| Operating altitude | ≤ 2000 m |
| Power consumption | ≤1.8 W |
| Protection degree | IP20 |
| Step response time | ≤ 5 ms |
| Temperature coefficient | <0.01% of span/°C (TU) |
| Type of connection | Screw connection |
| Type of signal forwarding according to HART® | unchanged |
| Voltage supply | 19.2…31.2 V DC |
| EMC standards | EN 61326-1 |
| Insulation voltage | 2.6 kV (input / output) |
| Rated voltage | 300 V |
| Standards | EN 61010-1 |
| Current I0 | 93 mA |
| Installation location | Device installed in safe area, zone 2 |
| Marking | II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Power P0 | <650 mW |
| Voltage U0 | 28 V DC |
| Description of the “safe state” | analogue Output ≤ 3.6 mA or output ≥ 21 mA |
| Device type | A |
| Tproof | 5 a |
| Total failure rate for safe detected failures (λSD) | 0 FIT |
| Hardware fault tolerance (HFT) | 0 |
| Safety category | SIL 2 |
| Safe Failure Fraction (SFF) | 85 % |
| Mean Time To Repair (MTTR) | 24 h |
| Total failure rate for safe undetected failures (λSU) | 164 FIT |
| Total failure rate for dangerous detected failures (λDD) | 127 FIT |
| Total failure rate for dangerous undetected failures (λDU) | 48 FIT |
| Probability of outage PFH | 4.8 x 10-8 h-1 |
| Demand mode | High |
| Average Probability of Failure on Demand (PFDavg) | 2.29 x 10-4 (Tproof = 1 year) 4.37 x 10-4 (Tproof = 2 years) 1.06 x 10-4 (Tproof = 5 year) |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.25 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 26 |
| Wire connection cross section AWG, max. | AWG 12 |
| Time interval | 3 years |
| Long specification | Ex output isolation amplifier for standard DC current signals, 2-channel, HART transparent2-channel output isolation amplifier in 22.5 mm width with external power supply,for transmitting and isolating standard signals 4 to 20 mA from the safe zone to Ex zones 0,1,2. Status-/ error messages are available via a relay contact (NO).The component can be configured using standard FDT/DTM software.Add-on housing for TS35 rail mountingDimensions: L/W/H 119.2/ 22.5/ 113.6Screw connection/ Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 2 x 4…20 mA Output 2 x 4…20 mALoad < 600 Ohm KanalAccuracy < 0,1 % v.ETemperature coefficient < 0,01% v.E./°C (Tu) Alarm output relay 1 NO contact 250 V AC / 30 V DC @ 2A safe zone 32 V AC @ 0.5 A/ 32 VDC @ 1 A Zone 2Auxiliary power 19…31.2 V DCPower loss approx. 3 WAmbient temperature range -20 °C…+60 °C Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, ATEX IECEX, FMATEX marking II 3 G ExnA nC IIC T4ATEX characteristic data U0 = 28 V DC I0 = 93 mA DC P0 = 650 mWType ACT20X-2SAI-2HAO-S |
| Short specification | Ex output isolation amplifier for standard DC current signals, 2-channel, HART transparent2-channel output isolation amplifier in 22.5 mm width with external power supply,for transmitting and isolating standard signals 4 to 20 mA from the safe zone to Ex zones 0,1,2. Status-/ error messages are available via a relay contact (NO).The component can be configured using standard FDT/DTM software. |