Weidmueller ACT20X-HDI-SDO-RNO-S

Request a price

ACT20X-HDI-SDO-RNO-S

SKU: 8965340000.0 Category: Brand:

EX signal isolating converter, Ex-input: NAMUR sensor/switch, Safe-output: relay, NO contact, 1-channel

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 119.2 mm
Height (inches) 4.693 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 177 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL PAPER SIL certificate
SIL in compliance with IEC 61508 2
MTBF 207 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting Snap mounting support rail
Input frequency <20 Hz
Input resistance 1 kΩ
NAMUR supply 8 V DC / 8 mA
Output signal in case of wire break 6.5 mA (in case of wire break)
Pulse duration > 0.1 ms
Resistance RP = 750 Ω / RS = 15kΩ
Sensor NAMUR sensor, according to EN60947-5-6 switch with or without RS, RP
Sensor supply 8 V DC / 8 mA
Trigger level high > 2.1 mA
Trigger level low <1.2 mA
Type intrinsically safe circuit
Continuous current ≤ 2 A AC/DC (safe area, Zone 2 area)
Function Output = input direct or inverse (configurable)
Max. switching frequency 20 Hz
Nominal switching voltage ≤ 250 V AC / 30 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Switching capacity 500 VA / 60 W (safe area) 16 VA / 60 W (zone 2)
Type Relay, 1 NO Switching frequency 20 Hz
Alarm function Line interruption at the input Short circuit at input No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Status relay 1 NC (voltage-free)
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤ 1.3 W
Protection degree IP20
Type of connection Screw connection
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 12 mA DC
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Power P0 32 mW
Voltage U0 10.6 V DC
Description of the “safe state” de-energized (relay output)
Device type B
Diagnostic test interval 10 s
Tproof 4 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Relay lifetime 100000 times
Safe Failure Fraction (SFF) 90 %
Mean Time To Repair (MTTR) 8 h
Total failure rate for safe undetected failures (λSU) 289 FIT
Total failure rate for dangerous detected failures (λDD) 130 FIT
Total failure rate for dangerous undetected failures (λDU) 46 FIT
Probability of outage PFH 4.66 x 10-8 h-1
Demand mode High
Demand rate 1,000 s
Demand response time <10 ms (relay output)
Safe Failure Fraction (SFF) 90 %
Average Probability of Failure on Demand (PFDavg) 2.04 x 10-4 (Tproof = 1 year) 4.08 x 10-4 (Tproof = 2 years) 1.02 x 10-4 (Tproof = 5 years)
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.25 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 12
Time interval 3 years
Long specification Ex isolating switch amplifiers for Namur sensors1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1,2 into the safe zone. On the output side there is a potential-free relay contact with closing function and an alarm contact forstatus/error messages.The component can be configured using standard FDT/DTM software.Add-on housing for TS35 DIN rail installationDimensions: L/W/H 119.2/ 22.5/ 113.6Screw connection/ nominal cross-section 2.5 mm2Protection degree: IP20 Input NAMUR sensor according to EN 60947 8 VDC / 8 mA sensor power supply 0 to 5 kHz input frequency wire-break detectionOutput Relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2Alarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A/ 32 VDC @ 1 A zone 2Auxiliary power 19 to 31.2 VDCPower loss approx. 1.8 WAmbienttemperature range -20 °C to +60 °CSecure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G ExnA nC IIC T4 ATEX characteristic data U0 = 10, 6 V DC I0 = 12 mA DC P0 = 32 WType ACT20X-HDI-SDO-RNO-S
Short specification Ex isolating switch amplifiers for Namur sensors1-channel isolating switch amplifiers in 22.5 mm width with an external power supply,to transmit and isolate Namur sensor signals from Ex zones 0,1,2 into the safe zone. On the output side there is a potential-free relay contact with closing function and an alarm contact forstatus/error messages.The component can be configured using standard FDT/DTM software.

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20X-HDI-SDO-RNO-S”