Weidmueller ACT20X-HTI-SAO-S

Request a price

ACT20X-HTI-SAO-S

SKU: 8965470000.0 Category: Brand:

EX signal isolating converter, Ex-input: I,ϑ, Safe-output: 4-20mA, 2-channel, Input : Temperature, 0-20 mA, EX, Output : 0(4)-20 mA, Safe, 4-20 mA

Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 119.2 mm
Height (inches) 4.693 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 178 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL PAPER SIL certificate
SIL in compliance with IEC 61508 2
MTBF 111 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting DIN rail Snap mounting support rail
Input current 0…20 mA 4…20mA
Input resistance, current 20 Ω + PTC 50 Ω
Line resistance in measuring circuit ≤ 50 Ω
Sensor 2-/3-/4-wire RTD: PT10, PT20, PT50, PT100, PT250, PT300, PT400, PT500, PT1000, Ni50, Ni100, Ni120, Ni1000 Thermocouples: B, E, J, K, N, R, S, T ; in compliance with IEC 60584-1 and L, U in compliance with DIN43710
Temperature input range Configurable PT100: -200…+850 °C K: (-180…+1372 °C) L: (-200…+900 °C) N: (-180…+1300 °C) R: (-50…+1760 °C) S: (-50…+1760 °C) T: (-200…+400 °C) U: (-200…+600 °C) W3: (0…+2300 °C) W5: (0…+2300 °C) LR: (-200…+800 °C) PT200: -200…+850 °C PT1000: -200…+850 °C NI100: -60°C…+250 °C Ni120: -80 °C…+320 °C NI1000: -60°C…+250 °C B: +100…+1820 °C E: (-100…+1000 °C) J: (-100…+1200 °C)
Type intrinsically safe circuit RTD, TC, DC (mA)
Influence of load resistance ≤ 0.01% of span / 100 Ω
Load impedance current ≤ 600 Ω
Output current 0…23 mA, configurable: 0…20 / 4…20 / 20…0 / 20…4 mA configurable downscale (3.5 mA) ⁄ upscale (23 mA) @ error
Output signal limit 3.8…20.5 mA / 0…20.5 mA (dependent on range)
Type active (as current source) or passive (as current sink)
Alarm function Line interruption at the input Short circuit at input No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Status relay 1 NC (voltage-free)
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤ 0.8 W
Protection degree IP20
Step response time ≤ 400 ms (with current) ≤ 1 s (with temperature)
Type of connection Screw connection
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 18.4 mA
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Power P0 40 mW
Voltage U0 8.7 V DC
Description of the “safe state” analogue Output ≤ 3.6 mA or output ≥ 21 mA
Device type B
Diagnostic test interval 30 s
Tproof 3 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Safe Failure Fraction (SFF) 90 %
Mean Time To Repair (MTTR) 24 h
Total failure rate for safe undetected failures (λSU) 234 FIT
Total failure rate for dangerous detected failures (λDD) 367 FIT
Total failure rate for dangerous undetected failures (λDU) 61 FIT
Probability of outage PFH 6.1 x 10-8 h-1
Demand mode High
Demand rate 3,000 s
Demand response time Signal input: <0.5 s (opto output) Temperature input: <1.1 s (opto output)
Average Probability of Failure on Demand (PFDavg) 3.96 x 10-4 (Tproof = 1 year) 6.5 x 10-4 (Tproof = 2 years) 1.41 x 10-4 (Tproof = 5 years)
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.25 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 12
Time interval 3 years
Short specification Ex- temperature transducer for RTD-/ TC temperature signals and DC current signals1-channel temperature transducer in 22.5 mm width with external power supply,for capturing and isolating RTD- / TC- sensor and DC current signals (0(4)…20 mA) from Ex zones 0,1,2. The output can be operated in the safe zone either as an active signal (0(4)…20 mA) or as a passive 4…20 mA current loop. Status and error messages are available via a relay contact (NO).The component can be configured using standard FDT/DTM software.

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20X-HTI-SAO-S”

Your email address will not be published. Required fields are marked *