Technical Specifications:

Depth 113.6 mm
Depth (inches) 4.472 inch
Height 127.1 mm
Height (inches) 5.004 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 170 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL in compliance with IEC 61508 2
MTBF 175 a
SFF 91 %
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting Snap mounting support rail
Input resistance, voltage 3.5 kΩ
Input voltage ≤ 28 V DC Trigger level low: ≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP) Trigger level high: ≥ 4.0 V DC (NPN), ≥ 10.0 V DC (PNP)
Number of inputs 1
Sensor NAMUR sensor, according to EN60947-5-6
Type NPN, PNP transistor, switching signal [input safe-side valve component]
Output current max. 60 mA
Output values depending on terminal assignment
Residual ripple (current loop) <40 mVeff
Type intrinsically safe circuit digital, output = input direct or inverse (configurable)
Max. switching frequency 20 Hz
Alarm function No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Type Status relay 1 NC (voltage-free)
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤ 1.9 W
Protection degree IP20
Step response time 10 ms
Type of connection PUSH IN
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 ≤ 135 mA
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Power P0 ≤ 0.77 W
Voltage U0 28 V DC
Description of the “safe state” de-energized (relay output)
Device type B
Diagnostic test interval 10 s
Tproof 4 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Safe Failure Fraction (SFF) 91 %
Mean Time To Repair (MTTR) 24 h
Total failure rate for safe undetected failures (λSU) 480 FIT
Total failure rate for dangerous detected failures (λDD) 61 FIT
Total failure rate for dangerous undetected failures (λDU) 46 FIT
Probability of outage PFH 4.6 x 10-8 h-1
Demand mode High
Demand rate 1,000 s
Demand response time <10 ms (opto output)
Average Probability of Failure on Demand (PFDavg) 2.92 x 10-4 (Tproof = 1 year) 4.84 x 10-4 (Tproof = 2 year) 1.06 x 10-4 (Tproof = 5 year)
Type of connection PUSH IN
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Time interval 3 years