EX signal isolating converter, 1-channel, Output current : max. 35 mA
Technical Specifications:
| Depth | 113.6 mm |
| Depth (inches) | 4.472 inch |
| Height | 119.2 mm |
| Height (inches) | 4.693 inch |
| Width | 22.5 mm |
| Width (inches) | 0.886 inch |
| Net weight | 170 g |
| Storage temperature | -20 °C…85 °C |
| Operating temperature | -20 °C…60 °C |
| Humidity | 0…95 % (no condensation) |
| SIL PAPER | SIL certificate |
| SIL in compliance with IEC 61508 | 2 |
| MTBF | 175 a |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Mounting position | horizontal or vertical |
| Rail | TS 35 |
| Type of mounting | Rail Snap mounting support rail |
| Input resistance, voltage | 3.5 kΩ |
| Input voltage | ≤ 28 V DC Trigger level low: ≤ 2.0 V DC (NPN), ≤ 8.0 V DC (PNP) Trigger level high: ≥ 4.0 V DC (NPN), ≥ 10.0 V DC (PNP) |
| Number of inputs | 1 |
| Type | NPN, PNP transistor, switching signal [input safe-side valve component] |
| Output current | max. 35 mA |
| Output values | Current: max.: 35 mA Voltage: min.: 12.5 V Current: max.: 35 mA Voltage: min.: 13.5 V Current: max.: 35 mA Voltage: min.: 14.5 V |
| Output values | depending on terminal assignment: 12.5 V @ 35 mA / 13.5 V @ 35 mA / 14.5 V @ 35 mA |
| Output values | depending on terminal assignment |
| Residual ripple (current loop) | <40 mVeff |
| Type | intrinsically safe circuit digital, output = input direct or inverse (configurable) |
| Max. switching frequency | 20 Hz |
| Alarm function | No supply voltage Device error |
| Continuous current | ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2) |
| Nominal switching voltage | ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2) |
| Power rating | ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2) |
| Type | Status relay 1 NC (voltage-free) |
| Configuration | With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB |
| Humidity | 0…95 % (no condensation) |
| Operating altitude | ≤ 2000 m |
| Power consumption | ≤ 1.9 W |
| Protection degree | IP20 |
| Step response time | 10 ms |
| Type of connection | Screw connection |
| Voltage supply | 19.2…31.2 V DC |
| EMC standards | EN 61326-1 |
| Insulation voltage | 2.6 kV (input / output) |
| Rated voltage | 300 V |
| Standards | EN 61010-1 |
| Current I0 | ≤ 110 mA |
| Installation location | Device installed in safe area, zone 2 |
| Marking | II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
| Power P0 | ≤ 0.77 W |
| Voltage U0 | 28 V DC |
| Description of the “safe state” | de-energized (relay output) |
| Device type | B |
| Diagnostic test interval | 10 s |
| Tproof | 5 a |
| Total failure rate for safe detected failures (λSD) | 0 FIT |
| Hardware fault tolerance (HFT) | 0 |
| Safety category | SIL 2 |
| Safe Failure Fraction (SFF) | 91 % |
| Mean Time To Repair (MTTR) | 24 h |
| Total failure rate for safe undetected failures (λSU) | 477 FIT |
| Total failure rate for dangerous detected failures (λDD) | 61 FIT |
| Total failure rate for dangerous undetected failures (λDU) | 43 FIT |
| Probability of outage PFH | 4.3 x 10-8 h-1 |
| Demand mode | High |
| Demand rate | 1,000 s |
| Demand response time | <10 ms (relay output) |
| Average Probability of Failure on Demand (PFDavg) | 2.73 x 10-4 (Tproof = 1 year) 4.52 x 10-4 (Tproof = 2 years) 9.89 x 10-4 (Tproof = 5 years) |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.25 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 26 |
| Wire connection cross section AWG, max. | AWG 12 |
| Time interval | 3 years |
| Long specification | Ex valve control modules, 35 mA ignition protection group IIC 1-channel valve control modules in 22.5 mm width with external power supply, to control valves in Ex areas zone 0,1,2 from the safe zone. The module comes with full three-way, 2.6 kV separation. On the input side, NPN/PNP switching sensors can be connected. On the output side, there are three 35 mA driver steps for ignition protection group IIC with a minimum driver voltage of 12.5 V/13.5 V or 14.5 V available optionally. An additional alarm contact (“a” contact) reports status and error messages The module can be configured using standard FDT/DTM software. Add-on housing for TS35 DIN rail installation Dimensions: L/W/H 119.2/ 22.5/ 113.6screw connection / nominal cross-section 2.5 mm2Protection degree: IP20 input NPN, PNP switch signal max. 28 VDC output Ex Imax 35 mA @ ignition protection group IIC U with load min. 12.5 V / min. 13.5 V / min. 14.5 V U without load min. 24 V alarm output relay 1 NO contact 250 VAC / 30 VDC @ 2A safe zone 32 VAC @ 0.5 A / 32 VDC @ 1 A zone 2Auxiliary power 19 to 31.2 VDC Power loss approx. 1.8 W Ambient temperature range -20 °C to +60 °C Secure isolation EN 61010, 3-way isolation up to 2.6 kV AC/DC of all circuits against each otherWorking voltage 300 V AC/DC at overvoltage category II and pollution degree 2 Approvals cULus, ATEX IECEX, FM ATEX marking II 3 G ExnA nC IIC T4 ATEX characteristic data U0 = 28 V DC I0 = 110 mA P0 = 0.77 W Type ACT20X-SDI-HDO-L-S |
| Short specification | Ex valve control modules, 35 mA ignition protection group IIC1-channel valve control modules in 22.5 mm width with external power supply,to control valves in Ex zones 0,1,2 from the safe zone. The module comes with full three-way, 2.6 kV separation. On the input side, NPN/PNP switching sensors can be connected. On the output side, there are three 35 mA driver steps for ignition protection group IIC witha minimum driver voltage of 12.5 V/13.5 V or 14.5 V available optionally. An additional alarm contact (“a” contact) reports status and error messagesThe module can be configured using standard FDT/DTM software. |





Reviews