SKU: 2472170000.0 Category: Brand:

Printed circuit board terminals, 7.50 mm, Number of poles: 11, 90°, Solder pin length (l): 5 mm, tinned, black, PUSH IN with actuator, Clamping range, max. : 6 mm², Box

Technical Specifications:

Depth 22.07 mm
Depth (inches) 0.869 inch
Height 36.55 mm
Height (inches) 1.439 inch
Height of lowest version 31.55 mm
Width 83.5 mm
Width (inches) 3.287 inch
Net weight 39.63 g
RoHS Compliance Status Compliant without exemption
REACH SVHC No SVHC above 0.1 wt%
Product family OMNIMATE Power – series LL
Wire connection method PUSH IN with actuator
Mounting onto the PCB THT solder connection
Conductor outlet direction 90°
Pitch in mm (P) 7.5 mm
Pitch in inches (P) 0.295 “
Number of poles 11
Pin series quantity 1
Fitted by customer No
Number of rows 1
Solder pin length (l) 5 mm
Solder pin dimensions d = 1.5 mm
Solder eyelet hole diameter (D) 2 mm
Solder eyelet hole diameter tolerance (D) + 0,1 mm
Number of solder pins per pole 1
Stripping length 12 mm
L1 in mm 75 mm
L1 in inches 2.95 “
Touch-safe protection acc. to DIN VDE 0470 IP 20
Touch-safe protection acc. to DIN VDE 57 106 Safe from finger touch
Protection degree IP20
Insulating material Wemid (PA)
Colour black
Colour chart (similar) RAL 9011
Insulating material group I
UL 94 flammability rating V-0
Contact material Cu-alloy
Contact surface tinned
Layer structure of solder connection 4…10 µ Sn matt
Storage temperature, min. -40 °C
Storage temperature, max. 70 °C
Operating temperature, min. -40 °C
Operating temperature, max. 120 °C
Clamping range, min. 0.25 mm²
Clamping range, max. 6 mm²
Wire connection cross section AWG, min. AWG 24
Wire connection cross section AWG, max. AWG 8
Solid, min. H05(07) V-U 0.5 mm²
Solid, max. H05(07) V-U 6 mm²
Stranded, min. H07V-R 0.5 mm²
Flexible, min. H05(07) V-K 0.5 mm²
Flexible, max. H05(07) V-K 6 mm²
w. plastic collar ferrule, DIN 46228 pt 4, min. 0.25 mm²
w. plastic collar ferrule, DIN 46228 pt 4, max. 6 mm²
w. wire end ferrule, DIN 46228 pt 1, min. 0.25 mm²
w. wire end ferrule, DIN 46228 pt 1, max. 6 mm²
Clampable conductor Cross-section for conductor connection: Type: fine-wired nominal: 0.5 mm² wire end ferrule: Stripping length: nominal: 14 mm Recommended wire-end ferrule: 1076980000 Cross-section for conductor connection: Type: fine-wired nominal: 1 mm² wire end ferrule: Stripping length: nominal: 15 mm Recommended wire-end ferrule: 9025930000 Cross-section for conductor connection: Type: fine-wired nominal: 1.5 mm² wire end ferrule: Stripping length: nominal: 15 mm Recommended wire-end ferrule: 9019140000 Stripping length: nominal: 12 mm Recommended wire-end ferrule: 9004060000 Cross-section for conductor connection: Type: fine-wired nominal: 0.75 mm² wire end ferrule: Stripping length: nominal: 14 mm Recommended wire-end ferrule: 9025910000 Cross-section for conductor connection: Type: fine-wired nominal: 2.5 mm² wire end ferrule: Stripping length: nominal: 14 mm Recommended wire-end ferrule: 9019170000 Stripping length: nominal: 12 mm Recommended wire-end ferrule: 0186100000 Cross-section for conductor connection: Type: fine-wired nominal: 4 mm² wire end ferrule: Stripping length: nominal: 12 mm Recommended wire-end ferrule: 0244100000 Stripping length: nominal: 14 mm Recommended wire-end ferrule: 9019200000 Cross-section for conductor connection: Type: fine-wired nominal: 6 mm² wire end ferrule: Stripping length: nominal: 14 mm Recommended wire-end ferrule: 0533500000 Stripping length: nominal: 12 mm Recommended wire-end ferrule: 0191900000
Reference text Length of ferrules is to be chosen depending on the product and the rated voltage. The outside diameter of the plastic collar should not be larger than the pitch (P)
tested acc. to standard In accordance with IEC 60947-7-1
Rated current, min. number of poles (Tu=20°C) 41 A
Rated current, max. number of poles (Tu=20°C) 35 A
Rated current, min. number of poles (Tu=40°C) 41 A
Rated current, max. number of poles (Tu=40°C) 30 A
Rated voltage for surge voltage class / pollution degree II/2 1,000 V
Rated voltage for surge voltage class / pollution degree III/2 1,000 V
Rated voltage for surge voltage class / pollution degree III/3 1,000 V
Rated impulse voltage for surge voltage class/ pollution degree II/2 8 kV
Rated impulse voltage for surge voltage class/ pollution degree III/2 8 kV
Rated impulse voltage for surge voltage class/ contamination degree III/3 8 kV
Rated voltage (Use group B / CSA) 600 V
Rated voltage (Use group C / CSA) 600 V
Rated voltage (Use group D / CSA) 600 V
Rated current (Use group B / CSA) 35 A
Rated current (Use group C / CSA) 35 A
Rated current (Use group D / CSA) 5 A
Wire cross-section, AWG, min. AWG 24
Wire cross-section, AWG, max. AWG 8
Institute (cURus) CURUS
Certificate No. (cURus) E60693
Rated voltage (Use group B / UL 1059) 600 V
Rated voltage (Use group C / UL 1059) 600 V
Rated voltage (Use group D / UL 1059) 600 V
Rated current (Use group B / UL 1059) 35 A
Rated current (Use group C / UL 1059) 35 A
Rated current (Use group D / UL 1059) 5 A
Wire cross-section, AWG, min. AWG 24
Wire cross-section, AWG, max. AWG 8
Reference to approval values Specifications are maximum values, details – see approval certificate.
Packaging Box
VPE length 214 mm
VPE width 212 mm
VPE height 49 mm
Test Durability of markings Standard: IEC 60947-7-4 section 7.1.4 / 08.13 Test: mark of origin, type identification, type of material, pitch, durability, stripping length Evaluation: available
Test Clampable cross section Standard: IEC 60999-1 section 7 and 9.1 / 11.99, IEC 60947-1 section 8.2.4.5.1 / 03.11 Conductor type: Type of conductor and conductor cross-section: solid 0.5 mm² Type of conductor and conductor cross-section: stranded 0.5 mm² Type of conductor and conductor cross-section: solid 6 mm² Type of conductor and conductor cross-section: stranded 6 mm² Type of conductor and conductor cross-section: AWG 24/19 Type of conductor and conductor cross-section: AWG 24/1 Type of conductor and conductor cross-section: AWG 10/1 Type of conductor and conductor cross-section: AWG 10/19 Type of conductor and conductor cross-section: H07V-K10 Evaluation: passed
Test for damage to and accidental loosening of conductors Standard: IEC 60999-1 section 9.4 / 11.99, IEC 60999-1 section 9.5 / 11.99 Requirement: 0.3 kg Conductor type: Type of conductor and conductor cross-section: H05V-K0.5 Type of conductor and conductor cross-section: H05V-U0.5 Evaluation: passed Requirement: 0,4 kg Conductor type: Type of conductor and conductor cross-section: H07V-K1 Type of conductor and conductor cross-section: H07V-U1 Evaluation: passed Requirement: 0.7 kg Conductor type: Type of conductor and conductor cross-section: H07V-K2.5 Type of conductor and conductor cross-section: H07V-U2.5 Evaluation: passed Requirement: 0.9 kg Conductor type: Type of conductor and conductor cross-section: H07V-K4 Type of conductor and conductor cross-section: H07V-U4.0 Evaluation: passed Requirement: 1.4 kg Conductor type: Type of conductor and conductor cross-section: H07V-K6 Type of conductor and conductor cross-section: H07V-U6 Evaluation: passed
Pull-out test Standard: DIN EN 60999-1 section 9.5 / 12.00 Requirement: ≥20 N Conductor type: Type of conductor and conductor cross-section: H05V-K0.5 Type of conductor and conductor cross-section: H05V-U0.5 Evaluation: passed Requirement: ≥50 N Conductor type: Type of conductor and conductor cross-section: H07V-K2.5 Type of conductor and conductor cross-section: H07V-U2.5 Evaluation: passed Requirement: ≥60 N Conductor type: Type of conductor and conductor cross-section: H07V-K4 Type of conductor and conductor cross-section: H07V-U4.0 Evaluation: passed Requirement: ≥80 N Conductor type: Type of conductor and conductor cross-section: H07V-K6 Type of conductor and conductor cross-section: H07V-U6 Evaluation: passed Requirement: ≥35 N Conductor type: Type of conductor and conductor cross-section: H07V-K1 Type of conductor and conductor cross-section: H07V-U1 Evaluation: passed
IPC conformity Conformity: The products are developed, manufactured and delivered according international recognized standards and norms and comply with the assured properties in the data sheet resp. fulfill decorative properties in accordance with IPC-A-610 “Class 2”. Further claims on the products can be evaluated on request.
Notes Additional variants on request Rated current related to rated cross-section & min. No. of poles. Wire end ferrule without plastic collar to DIN 46228/1 Wire end ferrule with plastic collar to DIN 46228/4 P on drawing = pitch Rated data refer only to the component itself. Clearance and creepage distances to other components are to be designed in accordance with the relevant application standards. The test point can only be used as potential-pickup point. The single-position PCB terminal block can be used for voltages up to 1500 V (DC) and 1000 V (AC). The relevant device standard and the appropriate required clearances and creepage distances should be observed in the application Long term storage of the product with average temperature of 50 °C and maximum humidity 70%, 36 months

Reviews

There are no reviews yet.

Be the first to review “Weidmueller LLF 7.50/11/90V 5.0SN BK BX”

Your email address will not be published. Required fields are marked *