Technical Specifications:
| Depth | 48.5 mm |
| Depth (inches) | 1.909 inch |
| Height | 48.5 mm |
| Height (inches) | 1.909 inch |
| Width | 8 mm |
| Width (inches) | 0.315 inch |
| Net weight | 12.96 g |
| Storage temperature | -25 °C…55 °C |
| Ambient temperature | -5 °C…40 °C |
| Continuous operating temp., min. | -60 °C |
| Continuous operating temp., max. | 130 °C |
| RoHS Compliance Status | Compliant without exemption |
| REACH SVHC | No SVHC above 0.1 wt% |
| Material | Wemid |
| Insulating material | Wemid |
| Colour | beige |
| UL 94 flammability rating | V-0 |
| End cover plate required | Yes |
| Number of levels | 1 |
| Number of clamping points per level | 2 |
| Levels cross-connected internally | No |
| Rail | TS 35 TS 32 |
| Explosion-tested version | No |
| Installation advice | Direct mounting |
| Connection type, additional connection | Screw connection |
| Connection cross-section, stranded, max. | 16 mm² |
| Connection cross-section, stranded, min. | 1.5 mm² |
| Number of connections | 2 |
| Stripping length | 12 mm |
| Type of connection | Screw connection |
| Type of connection 2 | Screw connection |
| Wire connection cross section, finely stranded, max. | 16 mm² |
| Wire connection cross section, finely stranded, min. | 1.5 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max. | 10 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min. | 1.5 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. | 10 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. | 1.5 mm² |
| Wire connection cross-section, solid core, max. | 4 mm² |
| Wire connection cross-section, solid core, min. | 1.5 mm² |
| Certificate No. (CSA) | 12400-397 |
| Current size C (CSA) | 50 A |
| Voltage size C (CSA) | 600 V |
| Wire cross section max. (CSA) | 8 AWG |
| Wire cross section min. (CSA) | 22 AWG |
| TS 32 offset | 20 mm |
| TS 35 offset | 20 mm |
| Installation advice | Direct mounting |
| Rail | TS 35 TS 32 |
| Standards | IEC 60947-7-1 |
| Rated cross-section | 10 mm² |
| Rated voltage | 600 V |
| Rated DC voltage | 600 V |
| Rated current | 57 A |
| Current at maximum wires | 57 A |
| Standards | IEC 60947-7-1 |
| Certificate No. (UR) | E60693 |
| Conductor size Factory wiring max. (UR) | 8 AWG |
| Conductor size Factory wiring min. (UR) | 22 AWG |
| Conductor size Field wiring max. (UR) | 8 AWG |
| Conductor size Field wiring min. (UR) | 22 AWG |
| Current size C (UR) | 47 A |
| Voltage size C (UR) | 600 V |