Weidmueller PRO ECO3 240W 24V 10A II

Request a price

PRO ECO3 240W 24V 10A II

SKU: 3025630000.0 Category: Brand:

Power supply, switch-mode power supply unit, 24 V

Technical Specifications:

Depth 125 mm
Depth (inches) 4.921 inch
Height 130 mm
Height (inches) 5.118 inch
Width 48 mm
Width (inches) 1.89 inch
Net weight 770 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Start-up ≥ -40 °C
Humidity 5…95 % rel. humidity, no condensation
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 6c, 7a, 7cI
REACH SVHC Lead 7439-92-1 Lead monoxide 1317-36-8
SCIP cc530c6d-a7ac-41ec-a2b4-caa3b47dbe25
Certificate No. (cURus) E255651
AC input voltage range 3 x 320…3 x 575 V AC / 2 x 360…2 x 575 V AC
Connection system Screw connection
Current consumption in relation to the input voltage Voltage type: 3-phase AC Input voltage: 400 V Input current: 0.71 A Voltage type: 3-phase AC Input voltage: 500 V Input current: 0.61 A Voltage type: DC Input voltage: 450 V Input current: 0.58 A Voltage type: DC Input voltage: 800 V Input current: 0.34 A
DC input voltage range 450…800 V DC
Frequency range AC 45…65 Hz
Input fuse internal
Inrush current (typ.) 35 A
Line regulation (typ.) 1 %
Load regulation (typ.) 2 %
Nominal power consumption 269.7 VA
Rated input voltage 3 x 400…3 x 500 V AC (wide-range input)
Recommended back-up fuse 2 A / DI, safety fuse4 A, Char. B, circuit breaker2…3 A, Char. C circuit breaker
Start-up time, max. 1 s
Surge protection Varistor
Wire connection method Screw connection
Capacitive load unrestricted
Connection system Screw connection
Continuous output current @ UNominal 6.25 A @ 70°C
Line regulation (typ.) 1 %
Load regulation (typ.) 2 %
Mains failure bridge-over time Mains failure bridge-over time, min.: 28 ms Input voltage type: AC Input voltage: 400 V Output current: 10 A Output voltage: 24 V Mains failure bridge-over time, min.: 53 ms Input voltage type: AC Input voltage: 500 V Output current: 10 A Output voltage: 24 V
Max. residual ripple <50 mVPP / bandwidth 20 MHz
Nominal output current for Unom 10 A @ 55 °C
Output power 240 W
Output voltage, max. 28 V
Output voltage, min. 22 V
Output voltage, note (adjustable via potentiometer)
Overload protection Yes
Parallel connection option yes, max. 3
Protection against inverse voltage Yes
Ramp-up time ≤ 100 ms
Rated output voltage 24 V DC
Wire connection method Screw connection
Degree of efficiency Typ.: 89,6% @ 400 V AC Typ.: 89% @ 480 V AC
Earth leakage current, max. 3.5 mA
Housing version Metal, corrosion resistant
Humidity 5…95 % rel. humidity, no condensation
Mounting position, installation notice on terminal rail TS 35
MTBF According to Standard: SN 29500 Operating time (hours), min.: 1,000,000 h Ambient temperature: 25 °C Input voltage: 400 V Output power: 240 W Duty cycle: 100 % According to Standard: SN 29500 Operating time (hours), min.: 500,000 h Ambient temperature: 40 °C Input voltage: 400 V Output power: 240 W Duty cycle: 100 % According to Standard: SN 29500 Operating time (hours), min.: 250,000 h Ambient temperature: 60 °C Input voltage: 400 V Output power: 240 W Duty cycle: 100 %
Power factor Power factor typical: 0.58 Input voltage: 400 V Ambient temperature: 25 °C Output power: 240 W
Power loss, idling 5.5 W
Power loss, nominal load 30 W
Protection against over-heating Yes
Protection against reverse voltages from the load 30…35 V DC
Protection degree IP20
Short-circuit protection Yes
Surge voltage category II
Interference immunity test acc. to EN 61000-4-2 (ESD) EN 61000-4-3 (RS) IEC 61000-6-4 EN 61000-4-4 (burst) EN 61000-4-5 (surge) EN 61000-4-6 (conducted) EN61000-4-8 (Fields) EN 61000-4-11 (Dips) IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3
Limiting of mains voltage harmonic currents EN 61000-3-2
Noise emission in accordance with EN55032 Class B
Shock resistance IEC 60068-2-27 30 g in all directions
Vibration resistance IEC 60068-2-6 0.7 g
Insulation voltage input / earth 3 kV
Insulation voltage output / earth 0.5 kV
Insulation voltage, input/output 4 kV
Pollution severity 2
Protection class I, with PE connection
Surge voltage category II
Electrical machine equipment Acc. to EN60204
For use with electronic equipment Acc. to EN50178 / VDE0160
Protection against dangerous shock currents Acc. to VDE0106-101
Protective separation / protection against electrical shock VDE0100-410 / acc. to DIN57100-410
Safety extra-low voltage SELV acc. to IEC 61010-1 PELV acc. to IEC 61010-2-201
Safety transformers for switch-mode power supplies According to EN 61558-2-16
Conductor cross-section, AWG/kcmil , max. 10 AWG
Conductor cross-section, AWG/kcmil , min. 20 AWG
Conductor cross-section, flexible , min. 0.22 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.18 mm²
Connection system Screw connection
Number of terminals 4 for L1/L2/L3/PE
Screwdriver blade 0.8 x 4.0
Stripping length (input) 7 mm
Tightening torque, max. 0.6 Nm
Tightening torque, min. 0.5 Nm
Wire connection cross section, flexible (input), max. 4 mm²
Conductor cross-section, AWG/kcmil , max. 12 AWG
Conductor cross-section, AWG/kcmil , min. 26 AWG
Conductor cross-section, flexible , max. 4 mm²
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection
Number of terminals 4 (++ / –)
Screwdriver blade 0.6 x 3.5
Stripping length (output) 6 mm
Tightening torque, max. 0.6 Nm
Tightening torque, min. 0.5 Nm
Number of terminals 2
Stripping length (Signal) 8 mm
Wire connection cross-section, flexible (signal), max. 1.5 mm²
Wire connection cross-section, flexible (signal), min. 0.2 mm²
Wire cross-section, AWG/kcmil , max. 14
Wire cross-section, AWG/kcmil , min. 28 mm²
Wire cross-section, solid , max. 1.5 mm²
Wire cross-section, solid , min. 0.2 mm²
Contact load (NO contact) max. 30 V DC / 1 A
Floating contact Yes
LED green Operating voltage OK

Reviews

There are no reviews yet.

Be the first to review “Weidmueller PRO ECO3 240W 24V 10A II”

Your email address will not be published. Required fields are marked *