Weidmueller TRS 24VUC 2CO FG

Request a price

TRS 24VUC 2CO FG

SKU: 2706290000.0 Category: Brand:

TERMSERIES, Relay module with positively driven contacts, Number of contacts: 2, CO contacts forcibily guided (EN 61810-3 type B) AgNi, Rated control voltage: 24 V UC ±10 %, Continuous current: 6 A, Screw connection, Test button available: No

Technical Specifications:

Depth 97.5 mm
Depth (inches) 3.839 inch
Height 89.6 mm
Height (inches) 3.528 inch
Width 12.8 mm
Width (inches) 0.504 inch
Net weight 62.4 g
Storage temperature -25 °C…70 °C
Operating temperature -25 °C…60 °C
Humidity 5…85 %, no condensation
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 9e2cbc49-76d9-4611-b8ec-5b4f549a0aa9
Ambient temperature (operational), max. 60 °C
Connection cross-section AWG, min. AWG 26
Connection cross-section AWG, max. AWG 14
Type of conductor rigid copper conductor flexible copper conductor
Tightening torque, max. 0.4 Nm
Pollution severity level 2
Rated control voltage 24 V UC ±10 %
Rated current AC 24.4 mA
Rated current DC 23.5 mA
Power rating 585 mVA 565 mW
Status indicator Green LED
Protective circuit Rectifier
Coil voltage of the replacement relay deviating from the rated control voltage Yes
Coil voltage of the replacement relay 24 V DC
Rated switching voltage 250 V AC
Continuous current 6 A
Max. switching frequency at rated load 0.1 Hz
Max. switching voltage, AC 250 V
Max. switching voltage, DC 250 V
Min. switching power 10 mA @ 5 V
AC switching capacity (resistive), max. 1500 VA
DC switching capacity (resistive), max. 144 W @ 24 V
Switch-on delay ≤ 30 ms
Switch-off delay <20 ms
Contact type 2 CO contacts forcibily guided (EN 61810-3 type B) (AgNi)
Mechanical service life 10 x 106 switching cycles
Operating altitude ≤ 2000 m above sea level
Rail TS 35
Test button available No
Mechanical switch position indicator No
Colour black
Rated voltage 300 V
Pollution severity 2
Surge voltage category III
Clearance and creepage distances for control side – load side ≥ 6 mm
Dielectric strength for control side – load side 3.51 kVeff /1 min.
Type of isolation at input and output reinforced insulation
Dielectric strength of neighbouring contacts 2.21 kVeff/ 1 min
Type of isolation at neighbouring contacts Basic insulation
Dielectric strength of open contact 1.5 kVeff /1 min.
Dielectric strength to mounting rail 3.51 kVeff / 1 min.
Impulse withstand voltage at neighbouring contacts 4 kV (1.2/50 µs)
Protection degree IP20
Standards EN 61326-1 EN 61010-2-201
Certificate no. (cULus) E141197
Wire connection method Screw connection
Stripping length, rated connection 8 mm
Tightening torque, max. 0.4 Nm
Clamping range, rated connection 1.5 mm²
Clamping range, min. 0.14 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.14 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire cross-section, solid, min. (AWG) AWG 26
Wire cross-section, solid, max. (AWG) AWG 14
Wire connection cross section, finely stranded, min. 0.14 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire cross-section, finely stranded, min. (AWG) AWG 26
Wire cross-section, finely stranded, max. (AWG) AWG 14
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.25 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), min. 0.25 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 2.5 mm²
Wire connection cross section, finely stranded, two clampable wires, min. 0.5 mm²
Wire cross-section, finely stranded, two clampable wires, max. 1 mm²
Twin wire-end ferrules, min. 0.5 mm²
Twin wire-end ferrules, max. 1 mm²
Blade size size PH0