Weidmueller VPU AC I 4 R 255/12.5 LCF MB

Request a price

VPU AC I 4 R 255/12.5 LCF MB

SKU: 2976650000.0 Category: Brand:

low voltage, Surge protection, Surge protection I / II, TN-C-S, TN-S

Technical Specifications:

Depth 65 mm
Depth (inches) 2.559 inch
Height 105 mm
Height (inches) 4.134 inch
Width 72 mm
Width (inches) 2.835 inch
Net weight 419 g
Storage temperature -40 °C…85 °C
Operating temperature -40 °C…85 °C
Humidity at operating temperature 5 – 95% rel. humidity
RoHS Compliance Status Compliant without exemption
REACH SVHC No SVHC above 0.1 wt%
Colour black
Design Installation housing; 4TE Insta IP 20
Operating altitude ≤ 4000 m
Optical function display green = OK; red = arrester is defective – replace
Protection degree IP20 in installed state
Rail TS 35
Segment Power distribution
UL 94 flammability rating V-0
Version low voltage Surge protection Surge protection I / II
Surge voltage category I III
Combined pulse UOC 6 kV
Discharge current (type III) 3 kA
Discharge current Imax (8/20µs) N-PE 100 kA
Discharge current Imax (8/20µs) wire-PE 50 kA
Discharge current In (8/20µs) N-PE 50 kA
Discharge current In (8/20µs) wire-PE 20 kA
Energy coordination (≤10 m) Type I Type II Type III
Follow-on current extinguishing capability Ifi 25 kA
Frequency range, max. 60 Hz
Frequency range, min. 50 Hz
Fuse No Fuse neccessary ≤250 A gG
Integrated back-up fuse No
Leakage current at Un 0 µA
Lightning test current Iimp (10/350 µs) (L-PE) 12.5 kA
Low voltage network TN-C-S TN-S
Max. continuous voltage, Uc (AC) 255 V
Number of poles 2
Protection level Up at IN (L/N-PE) ≤ 1.5 kV
Protection level Up at IN (N-PE) ≤ 1.5 kV
Rated voltage (AC) 230 V
Requirements category acc. to IEC 61643-11 Type I Type II
Requirements class, acc. to EN 61643-11 T1 T2
Response time <100 ns
Short-circuit current rating ISCCR 25 kA
Signalling contact 250 V 1A 1CO
Standards IEC 61643-11 EN 61643-11
Temporary surge voltage (over-voltage) – TOV 442 V
Voltage type AC
Stripping length 18 mm
Wire connection method Screw connection
Type of connection Screw connection
Tightening torque, min. 3 Nm
Tightening torque, max. 4.5 Nm
Clamping range, rated connection 16 mm²
Clamping range, min. 1.5 mm²
Clamping range, max. 35 mm²
Wire cross-section, solid, min. 1.5 mm²
Wire cross-section, solid, max. 35 mm²
Wire connection cross section, finely stranded, min. 1.5 mm²
Wire connection cross section, finely stranded, max. 35 mm²
Conductor cross-section, flexible, AEH (DIN 46228-1), max. 25 mm²
Connection cross-section, stranded, min. 1.5 mm²
Connection cross-section, stranded, max. 35 mm²
Voltage type AC
Number of poles 2
Protection degree IP20 in installed state
Colour black
Time interval 5 years

Reviews

There are no reviews yet.

Be the first to review “Weidmueller VPU AC I 4 R 255/12.5 LCF MB”

Your email address will not be published. Required fields are marked *