Measuring transformer disconnect terminal, Screw connection, 125, 2
Technical Specifications:
| Depth | 67.5 mm |
| Depth (inches) | 2.657 inch |
| Height | 100 mm |
| Height (inches) | 3.937 inch |
| Width | 16 mm |
| Width (inches) | 0.63 inch |
| Net weight | 110.22 g |
| Storage temperature | -25 °C…55 °C |
| Ambient temperature | -5 °C…40 °C |
| Continuous operating temp., min. | -50 °C |
| Continuous operating temp., max. | 120 °C |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 6c |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 0eb7d846-d0a1-43e5-93a4-d7c6856c4cda |
| Material | Wemid |
| Colour | blue |
| UL 94 flammability rating | V-0 |
| End cover plate required | No |
| Number of levels | 1 |
| Number of clamping points per level | 2 |
| Levels cross-connected internally | No |
| N-function | No |
| PE function | No |
| PEN function | Yes |
| Type of mounting | Snap-on |
| Clamping range, max. | 35 mm² |
| Clamping range, min. | 4 mm² |
| Connection cross-section, stranded, max. | 35 mm² |
| Connection cross-section, stranded, min. | 10 mm² |
| Connection direction | on side |
| Number of connections | 2 |
| Stripping length | 18 mm |
| Type of connection | Screw connection |
| Wire connection cross section AWG, max. | AWG 2 |
| Wire connection cross section AWG, min. | AWG 12 |
| Wire connection cross section, finely stranded, max. | 35 mm² |
| Wire connection cross section, finely stranded, min. | 4 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, max. | 35 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/1, min. | 4 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. | 35 mm² |
| Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. | 4 mm² |
| Wire connection cross-section, solid core, max. | 16 mm² |
| Wire connection cross-section, solid core, min. | 4 mm² |
| Cross-disconnect | without |
| Integral test socket | Yes |
| Slitting | sliding |
| Wire connection cross section AWG, max. | AWG 2 |
| Wire connection cross section AWG, min. | AWG 12 |
| Rated cross-section | 35 mm² |
| Rated voltage | 500 V |
| Rated DC voltage | 500 V |
| Rated current | 125 A |
| Current at maximum wires | 125 A |
| Volume resistance according to IEC 60947-7-x | 0.26 mΩ |
| Pollution severity | 3 |