Weidmueller ACT20M-CI-2CO-S

Request a price

ACT20M-CI-2CO-S

SKU: 1175990000.0 Category: Brand:

Signal splitter, Signal distributor, Input : 0(4)-20 mA, Output : 2 x 0(4) – 20 mA

Technical Specifications:

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 83.6 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation
SIL in compliance with IEC 61508 None
MTBF 219 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Input current 0…20 mA 4…20 mA
Input resistance, current 70 Ω
Number of inputs 1
Sensor Current source Sensor with own supply 4-wire sensor
Voltage drop, current input <1.5 V
Cut-off frequency (-3 dB) 100 Hz
Load impedance current <300 Ω per channel @ max 23mA
Number of outputs 2
Output current 0…20 mA 4…20 mA
Type active connected control must be passive
Accuracy <0.05 % of measuring range
Configuration none
Nominal power consumption 1.2 VA
Operating altitude ≤ 2000 m
Power consumption, max. 0.8 W
Power consumption, typ. 0.45 W
Protection degree IP20
Rail TS 35
Step response time ≤ 7 ms
Temperature coefficient ≤ 0.01 % / °C
Voltage supply 24 V DC ±30 % at terminal or via CH20M rail bus
EMC standards IEC 61326-1
Galvanic isolation 3-way isolator
Insulation voltage 2.5 kVeff /1 min.
Pollution severity 2
Rated voltage 300 Veff
Surge voltage category II
Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
EMC standards IEC 61326-1
Safety standard UL 61010-1
Ship use DNV-GL
Standards ATEX EN 60079-0 IECEX IEC 60079-0
Product information The non-adjustable DC isolating amplifier ACT20M-CI-CO-S isolates analogue standard current signals. An analogue input current signal is linearly converted to an analogue output current signal and is galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring or the Weidmüller rail bus. The non-adjustable DC isolation amplifier ACT20M CI-2CO-S offers the same functionality, but has 2 galvanically isolated outputs (4-way isolation).
Long specification Standard signal splitter1-channel signal splitter in 6.1 mm width with external power supply,to transmit, isolate and split analogue DC current signals 0/4…20 mAAdd-on housing for TS35 rail mountingDimensions: L/W/H 114.3/ 6.1/ 112.5 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 0/4…20 mAOutput 2 x 0/4…20 mA Load resistance < 300 Ohm/ AusgangTransmission error < 0,05 % v. E. Limit frequency 100 Hz Auxiliary power 24 VDC +/- 30 %Power loss approx. 0.8 WAmbient temperature range -25 °C…+70 °C Isolation EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each otherTest voltage 2.5 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, FM Div2, ATEX Zone2, DNV, GLType ACT20M-CI-2CO-S
Short specification Standard signal splitter1-channel signal splitter in 6.1 mm width with external power supply,to transmit, isolate and split analogue DC current signals 0/4 to 20 mA

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20M-CI-2CO-S”

Your email address will not be published. Required fields are marked *