Signal splitter, Signal distributor, Input : 0(4)-20 mA, Output : 2 x 0(4) – 20 mA
Technical Specifications:
| Depth | 114.3 mm |
| Depth (inches) | 4.5 inch |
| Height | 112.5 mm |
| Height (inches) | 4.429 inch |
| Width | 6.1 mm |
| Width (inches) | 0.24 inch |
| Net weight | 83.6 g |
| Storage temperature | -40 °C…85 °C |
| Operating temperature | -25 °C…70 °C |
| Humidity at operating temperature | 0…95 % (no condensation) |
| Humidity | 40 °C / 93 % rel. humidity, no condensation |
| SIL in compliance with IEC 61508 | None |
| MTBF | 219 a |
| RoHS Compliance Status | Compliant with exemption |
| RoHS Exemption (if applicable/known) | 7a, 7cI |
| REACH SVHC | Lead 7439-92-1 |
| SCIP | 2f6dd957-421a-46db-a0c2-cf1609156924 |
| Input current | 0…20 mA 4…20 mA |
| Input resistance, current | 70 Ω |
| Number of inputs | 1 |
| Sensor | Current source Sensor with own supply 4-wire sensor |
| Voltage drop, current input | <1.5 V |
| Cut-off frequency (-3 dB) | 100 Hz |
| Load impedance current | <300 Ω per channel @ max 23mA |
| Number of outputs | 2 |
| Output current | 0…20 mA 4…20 mA |
| Type | active connected control must be passive |
| Accuracy | <0.05 % of measuring range |
| Configuration | none |
| Nominal power consumption | 1.2 VA |
| Operating altitude | ≤ 2000 m |
| Power consumption, max. | 0.8 W |
| Power consumption, typ. | 0.45 W |
| Protection degree | IP20 |
| Rail | TS 35 |
| Step response time | ≤ 7 ms |
| Temperature coefficient | ≤ 0.01 % / °C |
| Voltage supply | 24 V DC ±30 % at terminal or via CH20M rail bus |
| EMC standards | IEC 61326-1 |
| Galvanic isolation | 3-way isolator |
| Insulation voltage | 2.5 kVeff /1 min. |
| Pollution severity | 2 |
| Rated voltage | 300 Veff |
| Surge voltage category | II |
| Installation location | Device installed in safe area, zone 2 |
| Marking | II 3 G Ex nA IIC T4 Gc |
| Type of connection | Screw connection |
| Tightening torque, min. | 0.4 Nm |
| Tightening torque, max. | 0.6 Nm |
| Clamping range, rated connection | 2.5 mm² |
| Clamping range, min. | 0.5 mm² |
| Clamping range, max. | 2.5 mm² |
| Wire connection cross section AWG, min. | AWG 30 |
| Wire connection cross section AWG, max. | AWG 14 |
| EMC standards | IEC 61326-1 |
| Safety standard | UL 61010-1 |
| Ship use | DNV-GL |
| Standards | ATEX EN 60079-0 IECEX IEC 60079-0 |
| Product information | The non-adjustable DC isolating amplifier ACT20M-CI-CO-S isolates analogue standard current signals. An analogue input current signal is linearly converted to an analogue output current signal and is galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) by means of direct wiring or the Weidmüller rail bus. The non-adjustable DC isolation amplifier ACT20M CI-2CO-S offers the same functionality, but has 2 galvanically isolated outputs (4-way isolation). |
| Long specification | Standard signal splitter1-channel signal splitter in 6.1 mm width with external power supply,to transmit, isolate and split analogue DC current signals 0/4…20 mAAdd-on housing for TS35 rail mountingDimensions: L/W/H 114.3/ 6.1/ 112.5 mmScrew connection / Nominal cross-section 2.5 mm2Protection degree: IP 20 Input 0/4…20 mAOutput 2 x 0/4…20 mA Load resistance < 300 Ohm/ AusgangTransmission error < 0,05 % v. E. Limit frequency 100 Hz Auxiliary power 24 VDC +/- 30 %Power loss approx. 0.8 WAmbient temperature range -25 °C…+70 °C Isolation EN 61010-1, 3-way isolation up to 2.5 kV AC/DC of all circuits against each otherTest voltage 2.5 kV input against output against auxiliary powerRated voltage 300 V AC/DC at overvoltage category II and pollution degree 2Approvals cULus, FM Div2, ATEX Zone2, DNV, GLType ACT20M-CI-2CO-S |
| Short specification | Standard signal splitter1-channel signal splitter in 6.1 mm width with external power supply,to transmit, isolate and split analogue DC current signals 0/4 to 20 mA |





Reviews