Weidmueller ACT20M-RTCI-CO-OLP-S

Request a price

ACT20M-RTCI-CO-OLP-S

SKU: 1435590000.0 Category: Brand:

Passive isolator, With galvanic isolation, Input : Temperature, PT100, thermocouple, Output : 4-20 mA

Technical Specifications:

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 80 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation
MTBF 207 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Influence of the sensor cable resistance <0.002 Ω/Ω
Line resistance in measuring circuit 50 Ω@ RTD (Pt100) 10 kΩ @ TC (J, K)
Number of inputs 1
Sensor PT100 (2-/3-/4- wire) Thermocouples: J, K
Temperature input range Configurable PT100: -200…+850 °C min. measurement range 10°C (RTD) J: (-100…+1200 °C) K: (-180…+1372 °C) min. measurement range 50°C (TC)
Load impedance current ≤ 600 Ω
Number of outputs 1
Output current configurable 4…20 mA 20…4 mA
Supply voltage (output) 16,8 V…31,2 V
Type passive connected control must be active
Wire break detection Yes Configurable 3.5 mA / 23 mA / none
Accuracy absolute accuracy: <±0.05 % of the measurement range RTD (PT100) Basic accuracy: <±0.1 °C of the measurement range TC (J,K) Basic accuracy: <±0.5 °C of the measurement range
Cold-junction compensation error ±(2.0 °C + 0.4 °C x Δt) Δt = inside temperature – ambient temperature
Configuration DIP switch
Delivery state Setting parameters: Output Configuration: 4…20 mA (loop) Setting parameters: Sensor error detection Configuration: enabled Setting parameters: Output error level Configuration: downscale Setting parameters: Noise suppression Configuration: 50 Hz Setting parameters: Step response time Configuration: < 30 ms Setting parameters: Start temperature Configuration: -200 °C Setting parameters: End temperature Configuration: 0 °C
Delivery state Output: 4…20 mA (loop) // Sensor error detection: enabled // Output error level: downscale // Noise suppression: 50 Hz // Step response time: < 30 ms // Start temperature: -200 °C // End temperature: 0 °C
Nominal power consumption 0.5 VA
Power consumption, max. 0.8 W
Power consumption, typ. 0.5 W
Protection degree IP20
Rail TS 35
Step response time Configurable ≤ 30 ms <300 ms
Temperature coefficient RTD (PT100) ≤0.01 % of the measurement range⁄°C or 0.02 °C ⁄ °C TC (J,K) 0.1 °C ⁄ °C
Voltage supply Output loop powered 6…35 V
EMC standards IEC 61326-1
Galvanic isolation 2-way isolator
Insulation voltage 2.5 kVeff /1 min.
Pollution severity 2
Rated voltage 300 Veff
Surge voltage category II
Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
EMC standards IEC 61326-1
Standards IEC 61010-1
Product information The ACT20M-RTCI-CO-OLP-S passive configurable temperature transducer isolates and converts analogue signals. An analogue RTD (Type Pt100) or TC (Type J, K) input signal is linearly converted into an analogue output signal and galvanically isolated. Power is supplied through the output measurement circuit (output- loop powered).

Reviews

There are no reviews yet.

Be the first to review “Weidmueller ACT20M-RTCI-CO-OLP-S”