Weidmueller ACT20M-RTI-AO-E-S

Request a price

ACT20M-RTI-AO-E-S

SKU: 1375520000.0 Category: Brand:

Temperature converter, Without galvanic isolation, Input : Temperature, PT100, Output : I / U

Technical Specifications:

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 86 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation
MTBF 195 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Influence of the sensor cable resistance <0.002 Ω/Ω (@ 3/4-wire)
Line resistance in measuring circuit ≤ 50 Ω
Number of inputs 1
Sensor PT100 (2-/3-/4- wire)
Temperature input range Configurable PT100: -200…+850 °C min. measurement range 10°C (RTD)
Load impedance current ≤ 600 Ω
load impedance voltage ≥ 10 kΩ
Number of outputs 1
Output current configurable 0…20 mA 4…20 mA
Output signal limit <4 mA (average), <60 mA (pulse current), low duty cycle
Output voltage, note configurable 0(2)…10 V 0(1)…5 V
Type active connected control must be passive
Wire break detection Yes Configurable 3.5 mA / 23 mA / none
Accuracy absolute accuracy: <±0.1 % of the measurement range
Configuration DIP switch
Delivery state Setting parameters: Input Configuration: 0…10 V Setting parameters: Bandwidth Configuration: 50 Hz Setting parameters: Output Configuration: 0…20 mA Setting parameters: Output 2 Configuration: 0…20 mA Setting parameters: Noise suppression Configuration: enabled Setting parameters: Start temperature Configuration: -200 °C Setting parameters: End temperature Configuration: 0 °C
Delivery state Input: 0…10 V // Bandwidth: 50 Hz // Output: 0…20 mA // Output 2: 0…20 mA // Noise suppression: enabled // Start temperature: -200 °C // End temperature: 0 °C
Nominal power consumption 0.5 VA
Operating altitude ≤ 2000 m
Power consumption, max. 0.5 W
Power consumption, typ. 0.37 W
Protection degree IP20
Rail TS 35
Step response time Configurable ≤ 30 ms <300 ms
Temperature coefficient ≤0.01 % of the measurement range⁄°C or 0.02 °C ⁄ °C
Voltage supply 24 V DC ± 30 %
EMC standards IEC 61326-1
Galvanic isolation Without isolation
Pollution severity 2
Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
EMC standards IEC 61326-1
Standards IEC 61010-1
Product information The ACT20M-RTI-AO-S configurable temperature transducer isolates and converts analogue signals. An analogue RTD input signal (Type Pt100) is linearly converted into an analogue output signal and galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) and this is done with direct wiring or over the Weidmüller rail bus. The ACT20M-RTI-AO-E-S configurable temperature transducer offers the same functionality but does not provide galvanic isolation.