Weidmueller ACT20M-TCI-AO-E-S

Request a price

ACT20M-TCI-AO-E-S

SKU: 1375500000.0 Category: Brand:

Temperature converter, Thermocouple, Without galvanic isolation, Input : Temperature, thermocouple, Output : I / U

Technical Specifications:

Depth 114.3 mm
Depth (inches) 4.5 inch
Height 112.5 mm
Height (inches) 4.429 inch
Width 6.1 mm
Width (inches) 0.24 inch
Net weight 86 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Humidity at operating temperature 0…95 % (no condensation)
Humidity 40 °C / 93 % rel. humidity, no condensation
MTBF 189 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Number of inputs 1
Sensor Thermocouples: J, K
Temperature input range Configurable J: (-100…+1200 °C) K: (-180…+1372 °C) min. measurement range 50°C (TC)
Load impedance current ≤ 600 Ω
load impedance voltage ≥ 10 kΩ
Number of outputs 1
Output current configurable 0…20 mA 4…20 mA
Output voltage, note configurable 0(2)…10 V 0(1)…5 V
Type active connected control must be passive
Wire break detection Yes Configurable 3.5 mA / 23 mA / none
Accuracy absolute accuracy: <±0.1 % of the measurement range Basic accuracy: <±1 °C
Configuration DIP switch
Delivery state Setting parameters: Input Configuration: 0 °C Setting parameters: Output 1 Configuration: 0…20 mA Setting parameters: Output 2 Configuration: 0…20 mA Setting parameters: Noise suppression Configuration: 100 Hz Setting parameters: Sensor error detection Configuration: enabled Setting parameters: Output error level Configuration: downscale Setting parameters: Step response time Configuration: < 30 ms
Delivery state Input: 0 °C // Output 1: 0…20 mA // Output 2: 0…20 mA // Noise suppression: 100 Hz // Sensor error detection: enabled // Output error level: downscale // Step response time: < 30 ms
Nominal power consumption 0.5 VA
Power consumption, max. 0.52 W
Power consumption, typ. 0.37 W
Protection degree IP20
Rail TS 35
Step response time Configurable ≤ 30 ms <300 ms
Temperature coefficient 0,1 °C ⁄ °C or ≤0,01% des Messbereichs⁄°C
Voltage supply 24 V DC ± 30 %
EMC standards IEC 61326-1
Galvanic isolation Without isolation
Pollution severity 2
Installation location Device installed in safe area, zone 2
Marking II 3 G Ex nA IIC T4 Gc
Type of connection Screw connection
Tightening torque, min. 0.4 Nm
Tightening torque, max. 0.6 Nm
Clamping range, rated connection 2.5 mm²
Clamping range, min. 0.5 mm²
Clamping range, max. 2.5 mm²
Wire connection cross section AWG, min. AWG 30
Wire connection cross section AWG, max. AWG 14
EMC standards IEC 61326-1
Standards IEC 61010-1
Product information The ACT20M-TCI-AO-S configurable temperature transducer isolates and converts analogue signals. An analogue thermocouple input signal (Type J, K) is linearly converted into an analogue output signal and is galvanically isolated. The power supply is galvanically isolated from the input and output (3-way isolation) and this is done with direct wiring or over the Weidmüller rail bus. The ACT20M-TCI-AO-E-S configurable temperature transducer offers the same functionality but does not have galvanic isolation.