Weidmueller ACT20X-2SAI-2HAO-P

Request a price

ACT20X-2SAI-2HAO-P

SKU: 2456170000.0 Category: Brand:

EX signal isolating converter, HART® transparency, 2-channel, Safe-input: 4-20mA, Ex output: 4 – 20 mA

Technical Specifications:

Depth 114.6 mm
Depth (inches) 4.512 inch
Height 127.3 mm
Height (inches) 5.012 inch
Width 22.5 mm
Width (inches) 0.886 inch
Net weight 212 g
Storage temperature -20 °C…85 °C
Operating temperature -20 °C…60 °C
Humidity 0…95 % (no condensation)
SIL PAPER SIL certificate
SIL in compliance with IEC 61508 2
MTBF 135 a
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 7a, 7cI
REACH SVHC Lead 7439-92-1
SCIP 2f6dd957-421a-46db-a0c2-cf1609156924
Mounting position horizontal or vertical
Rail TS 35
Type of mounting TS 35
Input current 4…20mA
Number of inputs 2
Voltage drop <2 V
2-wire supply > 14.5 V @ 20 mA
Influence of load resistance ≤ 0.01% of span / 100 Ω
Load impedance current ≤ 725 Ω
Output current 4…20 mA (max. 23 mA)
Output signal limit <28 mA
Residual ripple (current loop) <7.5 mVeff
Type intrinsically safe circuit
Max. switching frequency 0 Hz
Alarm function Signal limit exceeded Line interruption at the input No supply voltage Device error
Continuous current ≤ 0.5 A AC / 0.3 A DC (safe zone) ≤ 0,5 A AC / 1 A DC (zone 2)
Hysteresis 0.1 mA (switching threshold)
Nominal switching voltage ≤ 125 V AC / 110 V DC (safe area)≤ 32 V AC / 32 V DC (zone 2)
Power rating ≤ 62.5 VA / 32 W (safe area)≤ 16 VA / 32 W (Zone 2)
Switching thresholds 0…29.9 mA (programmable)
Type Status relay 1 NC (voltage-free)
Accuracy <0.1% span
Configuration With FDT/DTM software Requires configuration adapter 8978580000 CBX200 USB
HART® transparency supported Yes
Humidity 0…95 % (no condensation)
Operating altitude ≤ 2000 m
Power consumption ≤1.8 W
Protection degree IP20
Step response time ≤ 5 ms
Temperature coefficient <0.01% of span/°C (TU)
Type of connection PUSH IN
Type of signal forwarding according to HART® unchanged
Voltage supply 19.2…31.2 V DC
EMC standards EN 61326-1
Insulation voltage 2.6 kV (input / output)
Rated voltage 300 V
Standards EN 61010-1
Current I0 93 mA
Installation location Device installed in safe area, zone 2
Marking II (1) G [Ex ia Ga] IIC/IIB/IIA II (1) D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
Power P0 <650 mW
Voltage U0 28 V DC
Description of the “safe state” analogue Output ≤ 3.6 mA or output ≥ 21 mA
Device type A
Tproof 5 a
Total failure rate for safe detected failures (λSD) 0 FIT
Hardware fault tolerance (HFT) 0
Safety category SIL 2
Safe Failure Fraction (SFF) 85 %
Mean Time To Repair (MTTR) 24 h
Total failure rate for safe undetected failures (λSU) 164 FIT
Total failure rate for dangerous detected failures (λDD) 127 FIT
Total failure rate for dangerous undetected failures (λDU) 48 FIT
Probability of outage PFH 4.8 x 10-8 h-1
Demand mode High
Average Probability of Failure on Demand (PFDavg) 2.29 x 10-4 (Tproof = 1 year) 4.37 x 10-4 (Tproof = 2 years) 1.06 x 10-4 (Tproof = 5 year)
Type of connection PUSH IN
Wire connection cross section AWG, min. AWG 26
Wire connection cross section AWG, max. AWG 14
Wire cross-section, solid, min. 0.2 mm²
Wire cross-section, solid, max. 2.5 mm²
Wire connection cross section, finely stranded, min. 0.2 mm²
Wire connection cross section, finely stranded, max. 2.5 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, min. 0.2 mm²
Wire connection cross-section, finely stranded with wire-end ferrules DIN 46228/4, max. 2.5 mm²
Time interval 3 years