Technical Specifications:

Depth 100 mm
Depth (inches) 3.937 inch
Height 130 mm
Height (inches) 5.118 inch
Width 35 mm
Width (inches) 1.378 inch
Net weight 510 g
Storage temperature -40 °C…85 °C
Operating temperature -25 °C…70 °C
Start-up ≥ -40 °C
Humidity 5…95 % rel. humidity, no condensation
RoHS Compliance Status Compliant with exemption
RoHS Exemption (if applicable/known) 6c, 7a, 7cI
REACH SVHC Lead 7439-92-1 Lead monoxide 1317-36-8
SCIP cc530c6d-a7ac-41ec-a2b4-caa3b47dbe25
Certificate No. (cURus) E255651
AC input voltage range 85…264 V AC (derating at 100 V AC)
Connection system Screw connection
Current consumption in relation to the input voltage Voltage type: AC Input voltage: 100 V Input current: 2.17 A Voltage type: AC Input voltage: 240 V Input current: 1.08 A Voltage type: DC Input voltage: 120 V Input current: 1.15 A Voltage type: DC Input voltage: 370 V Input current: 0.41 A
DC input voltage range 110…370 V DC (derating at <120 V DC)
Frequency range AC 45…65 Hz
Input fuse internal
Inrush current (typ.) 40 A
Line regulation (typ.) 1 %
Load regulation (typ.) 2 %
Nominal power consumption 134.8 VA
Rated input voltage 100…240 V AC / 120…340 V DC
Recommended back-up fuse 3 A / DI, safety fuse6 A, Char. B, circuit breaker3…5 A, Char. C circuit breaker
Start-up time, max. 1 s
Surge protection Varistor
Wire connection method Screw connection
Capacitive load unrestricted
Connection system Screw connection
Continuous output current @ UNominal 3.125 A @ 70 °C
Line regulation (typ.) 1 %
Load regulation (typ.) 2 %
Mains failure bridge-over time Mains failure bridge-over time, min.: 118 ms Input voltage type: AC Input voltage: 230 V Output current: 5 A Output voltage: 24 V Mains failure bridge-over time, min.: 25 ms Input voltage type: AC Input voltage: 120 V Output current: 5 A Output voltage: 24 V
Max. residual ripple <50 mVPP / bandwidth 20 MHz
Nominal output current for Unom 5 A @ 55 °C
Output power 120 W
Output voltage, max. 28 V
Output voltage, min. 22 V
Output voltage, note (adjustable via potentiometer)
Overload protection Yes
Parallel connection option yes, max. 3
Protection against inverse voltage Yes
Ramp-up time ≤ 100 ms
Rated output voltage 24 V DC
Wire connection method Screw connection
Degree of efficiency Typ.: 88,4% @ 120 V AC Typ.: 90,1% @ 230 V AC
Earth leakage current, max. 3.5 mA
Housing version Metal, corrosion resistant
Humidity 5…95 % rel. humidity, no condensation
Mounting position, installation notice on terminal rail TS 35
MTBF According to Standard: SN 29500 Operating time (hours), min.: 3,200,000 h Ambient temperature: 25 °C Input voltage: 230 V Output power: 120 W Duty cycle: 100 % According to Standard: SN 29500 Operating time (hours), min.: 1,800,000 h Ambient temperature: 40 °C Input voltage: 230 V Output power: 120 W Duty cycle: 100 %
Power factor Power factor typical: 0.6 Input voltage: 120 V Ambient temperature: 25 °C Output power: 120 W Power factor typical: 0.5 Input voltage: 230 V Ambient temperature: 25 °C Output power: 120 W
Power loss, idling 1 W
Power loss, nominal load 15 W
Protection against over-heating Yes
Protection against reverse voltages from the load 30…35 V DC
Protection degree IP20
Short-circuit protection Yes
Surge voltage category II
Interference immunity test acc. to EN 61000-4-2 (ESD) EN 61000-4-3 (RS) IEC 61000-6-4 EN 61000-4-4 (burst) EN 61000-4-5 (surge) EN 61000-4-6 (conducted) EN61000-4-8 (Fields) EN 61000-4-11 (Dips) IEC 61000-6-1 IEC 61000-6-2 IEC 61000-6-3
Limiting of mains voltage harmonic currents According to EN 61000-3-2
Noise emission in accordance with EN55032 Class B
Shock resistance IEC 60068-2-27 30 g in all directions
Vibration resistance IEC 60068-2-6 0.7 g
Insulation voltage input / earth 3 kV
Insulation voltage output / earth 0.5 kV
Insulation voltage, input/output 4 kV
Pollution severity 2
Protection class I, with PE connection
Surge voltage category II
Electrical machine equipment Acc. to EN60204
For use with electronic equipment Acc. to EN50178 / VDE0160
Protection against dangerous shock currents Acc. to VDE0106-101
Protective separation / protection against electrical shock VDE0100-410 / acc. to DIN57100-410
Safety extra-low voltage SELV acc. to IEC 61010-1 PELV acc. to IEC 61010-2-201
Safety transformers for switch-mode power supplies According to EN 61558-2-16
Conductor cross-section, AWG/kcmil , max. 12 AWG
Conductor cross-section, AWG/kcmil , min. 26 AWG
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection
Number of terminals 3 for L/N/PE
Screwdriver blade 0.6 x 3.5
Stripping length (input) 6 mm
Tightening torque, max. 0.6 Nm
Tightening torque, min. 0.5 Nm
Wire connection cross section, flexible (input), max. 4 mm²
Conductor cross-section, AWG/kcmil , max. 12 AWG
Conductor cross-section, AWG/kcmil , min. 26 AWG
Conductor cross-section, flexible , max. 4 mm²
Conductor cross-section, flexible , min. 0.5 mm²
Conductor cross-section, rigid , max. 6 mm²
Conductor cross-section, rigid , min. 0.5 mm²
Connection system Screw connection
Number of terminals 4 (++ / –)
Screwdriver blade 0.6 x 3.5
Stripping length (output) 6 mm
Tightening torque, max. 0.6 Nm
Tightening torque, min. 0.5 Nm
Number of terminals 2
Stripping length (Signal) 8 mm
Wire connection cross-section, flexible (signal), max. 1.5 mm²
Wire connection cross-section, flexible (signal), min. 0.2 mm²
Wire cross-section, AWG/kcmil , max. 14
Wire cross-section, AWG/kcmil , min. 28 mm²
Wire cross-section, solid , max. 1.5 mm²
Wire cross-section, solid , min. 0.2 mm²
Contact load (NO contact) max. 30 V DC / 1 A
Floating contact Yes
LED green Operating voltage OK